Online transformer oil drying out system to remove moisture as well as solid contamination. It filters while transformer remains in charged state. Install and enhance the life of your transformer..
Other Specifications Download Specification | |
---|---|
Mode Of Working | Online |
Type | Portable |
Type Of Oil For Which Machine Is To Be Used For Cleaning | Transformer Oil |
Type Of Cleaning | Removal of Both Soild Contamination and Liquid Contamination |
Nominal Flow Rate | 500 LPH |
Centrifuge Pump Flow Rate | Centrifuge is not required in this technology hence NO MOTOR REQUIRED LPM |
Centrifuge Motor Capacity | 0.5 HP |
Centrifuge Make Of Motor | others Confirming to IS 325:1996 reaffirmed 2007 with ISI Marked |
Suction Pump Flow Rate | 20 LPM |
Suction Pump Motor Capacity | 1 HP |
Make Of Motor(Suction Pump) | others Confirming to IS 325:1996 reaffirmed 2007 with ISI Marked |
Discharge Pump Flow Rate | 20 LPM |
Discharge Pump Motor Capacity | 1 HP |
Make Of Motor( Discharge Pump) | others Confirming to IS 325:1996 reaffirmed 2007 with ISI Marked |
Dirt Holding Capacity | others grams |
Dirt Holding Capacity( For Others) | Removes Moisture grams |
Minimum Size Of Dirt( Including Metallic ,Non Metallic ,Suspended Soild Particle ) | upto 5 micron |
Length Of Inlet Wire Braided Hose Pipe | 5000 mm |
Diameter Of Inlet Wire Braided Hose Pipe | 10 mm |
Length Of Outlet Wire Braided Hose Pipe | 15000 mm |
Diameter Of Outlet Wire Braided Hose Pipe | 10 mm |
Vacuum Pump For First Stage | No |
Vacuum Pump For Second Stage | No |
Vacuum Pump Motor Capacity ( For First Stage ) | NA HP |
Vacuum Pump Motor Capacity ( For Second Stage ) | NA HP |
Vacuum Booster For First Stage | No |
Vacuum Booster For Second Stage | No |
Vacuum Booster Motor Capacity ( For First Stage ) | NA HP |
Vacuum Booster Motor Capacity ( For Second Stage ) | NA HP |
Vacuum Blower | No |
Vacuum Blower Motor Capacity | NA hp |
Moisture Separator | No |
If Yes Then Moisture Separating Capacity (otherwise Put NA) | NA ml |
Moisture Seperator Capacity (for Others ) | NA ml |
Operating Pressure ,Max | upto 5 Bar |
Operating Temperature | upto 60 Degree Celcius |
Heating System | Yes |
Heater Capacity | Heating System NOT REQUIRED kw |
Degassing Chamber | Yes |
Dimensions Of Degassing Chamber (Diameter X Height) | Degassing Chamber NOT REQUIRED mm x mm |
Capacity Of Degassing Chamber | Degassing Chamber NOT REQUIRED ltrs |
Ionic Reaction Cartridge | No |
Oil Reclamation Cartridge | No |
Water Adsorption Cartridge | Yes |
Filter Cartridge ( For Solid Contamination Removal Only) | Consumable |
Magnetic Strainer | No |
Length Of The Centrifugal Oil Cleaning Machine | 1250 Approx mm |
Width Of The CentrifugalOil Cleaning Machine | 700 Approx mm |
Height Of The Centrifugal Oil Cleaning Machine | 1850 Approx mm |
Weight Of The Centrifugal Oil Cleaning Machine | 500 Approx Kg |
Make Of Control Panel (All Parts) | Others Confirming to IS |
Dimensions Of Panel Box Confirming To IS 10322/1982Reaffirmed 2005( Length X Width X Height ) | others mm x mm x mm |
If Others Then Specify The Dimensions In LxWx H) | 500 X 250 X 500 Approx mm x mm x mm |
Thickness Of Panel Box Confirming To IS 10322/1982Reaffirmed 2005 | 250 Approx mm |
Online Moisture PPM Sensor | Yes |
Tramp Oil Skimmer | No |
Flowmeter | Yes |
Voltmeter (0-500 V) With Inbuilt Selector Switch | Yes |
Control Transformer | Yes |
Ammeter Digital 0-20 Amps | Yes |
Hours Counter Meter | Yes |
Indicator Light 3-ph | Yes |
No. Of Push Button | 2 |
Legent Plate 3mm Thick | Yes |
MCB TP 10-32 Amp | Yes |
MCB SP 2- Amp For Volt/Cont | Yes |
12 Amp Contactor 3 Pole | Yes |
O/L Relay 4-6.5 Amp | Yes |
Terminal Block 2.5 Mm | Yes |
Protection Relay Model -VSP-D1 | Yes |
Over Load Trip Indication 22.5 Mm Dia | Yes |
PVC Gland 13.5 /16x4x1.5 Mm | Yes |
Cable 4Cx 1.5 Mm(5 Meter) | Yes |
Machine Enclosure | Weather Proof |
Machine Wheels | Castor |
Lsit Of Standards Accessories Of Panel Box With Numbers To Be Provided | Indicator Light 3 phase - 3 Nos. Volt meter - 1 Nos. Amp. meter - 1 Nos. Hour Counter - 1 Nos. Push Button - 4 Nos. MCB TP 32 Amp - 1 Nos. MCB SP 6 Amp - 3 Nos. Contractor - 12 Amp 3 pole 2 Nos. O/L Relay - 2.5-4 Amp - 2 Nos. Protection relay - VSP- D-1 Cable Wire - 4C X 1.5mm2 |
Availability Of Test Report From Central Govt./NABL/ILAC Acredited Lab To Prove Confirmity To Specification | Yes |
Test Report No. | C-1498 |
Test Report Date | 30-June-2016 |
Name Of The Lab | Narang Metallurgical & Spectro Services |
Address Of The Lab | New Delhi |