"Product Catgeory","watermist and caf fire extinguisher high pressure trolley mounted" "Product Name","water mist and caf fire extinguisher high pressure trolley mounted" "Specification Title","Specification Value" ""Conformity to DIN EN 1866-1:2007-08 standards The complete system shall be tested for compliance from an internationally/nationally accredited laboratory for compliance to all 31 clauses (3.10, 6.1, 6.2.1, 6.2.2, 6.2.3, 6.3.1, 6.3.2, 6.3, 6.4.1-6.4.3, 6.4.4, 6.5, 6.6, 6.7, 6.8.1, 6.8.2, 6.8.3, 6.8.4, 6.8.6.1, 6.8.6.2, 6.8.6.3, 6.8.6.4, 6.8.6.5, 6.8.6.6, 6.9.1, 6.9.2, 6.10, 7.2.1, 7.2.2, 7.3, 8.1, 8.2 ) of DIN EN 1866-1:2007-08 Standard mandatorily applicable for the complete system. For trolley mounted configurations as clause no. 8.1.3 specified fire ratings shall be tested on portable fire extinguisher of same design from such laboratory as per EN 3 - 7:2004 + Al: 2007-08 (E)."",Yes "Trolley Mounted Type",Yes "The Trolley mounted configuration shall have water tank, compressed air cylinder and gun mounted on a free moving trolley provided with strong wheels as specified in DIN EN 1866-1:2007-08 Standards. Trolley mounted shall be supplied with two air cylinders.",Yes "Model Number as per Accredited Laboratory Test Report is to be declared","Hi press 02/050" "Air Cylinder Capacity",6 "Air Cylinder pressure",300 "Air Cylinder Material","Ultralight Carbon composite with PET Liner" "High Pressure Type (Dynamic Operating pressure above 30 bar to be tested in the accredited laboratory test report which will be considered as high pressure as per clause No. 3.15 of EN 3 - 7:2004 + Al: 2007-08 (E) Standard.)",30.4 "Type of Foam","Special AFFF Compound conforming to manufacturer own specifications for higher fire rating A55, B233, Spreading coefficient for special AFFF Compound shall be +5 minimum, concentration shall be 6%." "If special foam mention the compostion for special ,otherwise put NA","Special Foam : Water 96% 1.2-Ethandial" "Commercial Brand Name of the Special foam (fire extinguishing medium) as per accredited laboratory test report wherein IV B fire rating achieved, to be declared.","HNE Class A25-S (Special Foam)" "Characteristics of extinguishing medium of Special AFFF Compound with infrared spectrogram to be furnished.","Density : 1.117 Viscosity : 2.0 PH Factor 8.5 Refractive Index 13692 @ 20 + 2degC" "Fire Rating for Trolley Mounted IV B and Di Electric. With marking of Fire Class A & B as per EN 3-7 Standard",Yes "Pressure Vessel Material","Aluminum alloy" "Thickness of Material",8 "Capacity ( Nominal Charge )",50 "PED approval as per Directive 97/23/EC",YES "Pressure Vessel shall include a pressure gauge fitted on the vessel (CE Marked from notified body) to measure the air cylinder pressure.",YES ""No objection certificate (NOC) for Pressure Vessel from Petroleum and Explosives Safety Organization (PESO) Nagpur shall also be mandatory. "",YES "Pressure Vessel should have CE Marking from Notified body",YES "Extinguishing gun material","Stainless Steel" "if others Mentions the material for Extinguishing gun,otherwise put NA",NA "Extinguishing gun weight",750 "Lancing Distance of Gun ( with Tolerance of - 10% ,+ no limit ",15 "Length of EN marked Hose",5 "The air hoses shall be suitable for minus 40 deg C to 100 Deg C temperature and EN mark on hose",Yes "Operating time in full throttle",100 "Weight of fully charged Trolley Mounted system having Corrosion Free Aluminum Alloy vessel",105 "Main Components: Pressure vessel to hold the media with safety valve, compressed air cylinder coupled with a reducer, hose pipes for discharge of water mist media, extinguishing gun.",Yes ""System shall be designed for maximum operating temperature TSmax and minimum operating temperature TSmin of 60 deg C or more and 5 Deg C or less respectively and certified by the manufacturer accordingly as per Clause No. 6.1 of DIN EN 1866-1:2007-08 standards as per the accredited test report for Trolley mounted system "",Yes "Specific consent of the OEM for the value additions made along with a confirmation that fire ratings of the equipment would not be affected by these value additions.",Yes "Availability of Test Report to DIN EN 1866-1:2007-08 standards",Yes "Test Report No.","F-1/00 and 2009-F-3363/HNE08" "Test Report Date",06.12.2010 "Name of ILAC/NABL/Central Govt.Accredited Laboratory where Test Conducted","MPA Dresden" "NOC Letter No. Date of PESO Nagpur for Pressure Vessel","G.3(4)40/Misc/2009 dt. 01.01.2010"