The Megger MPQ 2000 Power Quality Analyzer is a highly intuitive advanced portable 3 phase AC-DC power analyser delivering unmatched capability in a NEMA4 IP54 weatherproof enclosure with IEC61000-4-30 Class A compliance having 5 current and 4 voltage channels. The unit is robust enough to remain recording outdoors, CAT IV at 600 V ensures a safe unit for all applications, Multiple communication methods USB, Ethernet, USB stick or SD card allow flexible and convenient operation, Rain Tight Flexible Current Clamps ranges includes 60 A, 600 A, 3000 A and 6000 A. It can measure RMS voltage/current, DC voltage/current requires DC CT upto 1000V, frequency, waveform capture, Power and Energy ParametersKW,KVAR, KVA, DPF, TPF, KWH, KVARH, KVAH, Inter and Power Harmonics, phase angle deviation, Flicker, Motor analysis and Inrush testing. For more information please refer datasheet of OEM. Warranty Three years on main instrument, one year on accessories. Price is inclusive of GST@18percent.
Other Specifications Download Specification | |
---|---|
Type Of Power Analyzer | Three phase |
Display Type | VGA Backlit |
Display Mode | Scope Mode and DVM Mode |
Number Of Current Channels | Five Nos. |
Number Of Voltage Channels | Four Nos. |
Facility To Measure RMS Voltage | Available |
Measurable Voltage Range | 0 to 1000V AC and V DC Volts |
Measurable Voltage Accuracy | 0.1percent Udin for 10percent to 150percent Udin |
Measurable Voltage Resolution | 16 Bit - .055V instantaneous reading Volts |
Facility To Measure RMS Current | Available |
Measurable Current Range | 0 to 6000A CT Dependent Ampere |
Measurable Current Accuracy | 1percent of reading per IEC61000-4-30 +CT |
Measurable Current Resolution | 0.000165 mautiply Ifs instantaneous reading Ampere |
Facility To Measure Active, Reactive And Apparent Power | Available |
Maximum Power That Can Be Measured | 18MW for 3 phases KW KW |
Power Accuracy | 1.75percent U multiply I + CT affects max maximum error due to 1degree phase error |
Power Resolution | 16 bit Watt Watt |
Facility To Measure Active, Reactive And Apparent Energy | Available |
Facility To Measure Sag(dips) And Swell(surge) | Available |
Facility To Measure Frequency | Available |
Frequency Range That Can Be Measured | 42.5-69 Hz Max harmonic freq 69 multiply 50 - 3450 Hz |
Facility To Measure Total Harmonic Distortion | Available |
Accuracy In Measurement Of Total Harmonics Distortion | 0.05 multiply THD or 0.35percent |
Resolution In Measurement Of Total Harmonics Distortion | 16 bit |
Facility To Measure Inter Harmonics | Available |
Order(n) To Which Facility To Measure Harmonics Available | 128 in software |
Facility To Measure Power Factor | Available |
Accuracy In Measurement Of Power Factor | 0.02 percent plus CT error |
Facility To Measure Distortion Factor | Available |
Accuracy In Measurement Of Distortion Factor | NA |
Facility To Measure Ripple Factor | Available |
Accuracy In Measurement Of Ripple Factor | NA |
Facility To Measure Voltage And Current Unbalance | Available |
Facility To Measure Inrush Current | Available |
Facility To Measure Flicker | Available |
Facility To Measure Crest Factor | Available |
Measurable Crest Factor Range | NA |
Measurable Crest Factor Accuracy | NA |
Measurable Crest Factor Resolution | NA |
Screen Memory | Yes |
Data Transfer Software Provided For Analysis On PC | Yes |
Internal Memory | Yes with SD Card MB |
Type Of Battery Used | NiMH Battery pack |
Battery Backup | 6.5 Hour Hours Hours |
Power Supply(volts In AC) | 230 |
Weight Of The Analyser | 2.27 Kg Grams Grams |
Dimensions(LXWXH) | 246x215x162mm cmXcmXcm |
Provision For External SD Card | Yes |
Operating Temperature Range | -20 to +50 degree celsius |
Operating Humidity | 0 -95 relative humidity non condensing % |
All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | Yes |
Details Of All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | USB memory stick -SD Card- Ethernet communication cable- Battery pack- unfused differential voltage lead kit |
Compliance To IEC 61000-4-30 | Yes |
Category Of Safety Rating | CAT IV- 600V |
Dry Heat Test As Per IS :9000(Part 3/Section 5) | Yes |
Damp Heat(cyclic Test): Two Cycles Of 24 Hours Each As Per IS: 9000(Part 5/section 1) | Yes |
Cold Test At -20 Degree C For Four Hours As Per IS: 9000(Part2 /section 4) | Yes |
Availability Of Type Test Report From Central Govt. /NABL/ILAC Accredited Lab. To Prove Confirmity To The Specification. | Yes |
Type Test Report No. | 214080 |
TTC Report Date | 11-2-2016 |
Name Of Lab | Megger Instruments Limited |
Address Of Lab | MEGGER LIMITED UK |
Interface | USB or Ethernet |