1.True Online UPS with Triple Conversion 2. Wide Input Voltage Range 3. Built-in OVCD for High Voltage Protection 4. Active Input Power Factor Corrector 5. Selectable Output Voltage 6. 0.8 output power factor 7. Built-in and External Battery Options 8. Advanced battery management ABM 9. Smart Battery Charger Design 10. Comprehensive Display for easy monitoring and access of UPS Status 11. Generator Compatible 12. Cold start feature DC power on 13. RS232/USB/SNMP LAN for UPS monitoring 14 ECO mode operation for energy saving 15. Self-diagnosis at UPS startup.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 1 KVA |
Technology | IGBT-PWM |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 216 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 3 % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | R-41046680 |
Type Test Certificate Date | 02/08/2016 |
Name Of Lab | BUREAU OF INDIAN STANDARD |
Address Of Lab | MANEK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG, NEW DELHI-110002 |
Supply & Commissioning | ON SITE |
Warranty | 2 Years |