Complete Blackout and Brownout ProtectionAccording to Study by Bells Labs, under voltage sudden dipsrepresent the majority of power problem. Wide Input range Onlinedesign of Uniline UPS prevent data loss caused by outrages brownouts.Salient Features Wide Input Windo Generator Compatible Computer Grade Power Superior Float Cum Boost Charger IGBT Based Hi - Frequency PWM Inverter O/P Distortion 3 Inverter Efficiency 92. High crest factor 4 1 Crystal controlled output frequency 50 Hz 0.01. Low noise 50 db upto 10 KVA Compact, sleek design Backup up to 8 Hrs RS 232 C / SNMP Interface Tested. by Reputed Agencies without batteries.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 5 KVA |
Technology | MOSFET-PWM with inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V 1 sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 4.5 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | No (only for IGBT-PWM Technology) |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 1 % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 38935D |
Type Test Certificate Date | 27.02.2014 |
Name Of Lab | NTH |
Address Of Lab | GHAZIABAD |
Supply & Commissioning | AS PER COMPANY |
Warranty | 1 Years |