dry chemical powder bc type cartridge type fire extinguisher 6 kg capacity (fire squad)(fs-09)

` 6,375.60

  • Offered Price: ` 7084.00
  • MRP: `7872.00

DRY CHEMICAL POWDER BC Type Cartridge Type Fire Extinguisher 6 Kg Capacity for class B C fire fitted with, cartridge type Squeeze lever discharge valve Complete with initial refill consisting of ISI Marked Co2 gas cartridge conforming to IS 4947 and ISI Marked Sodium base dry chemical powder conforming to IS 4308 Suitable for Operating between -10C to 55C IS 15683.

  • Availability: 200 In Stock
  • Min. Qty. Per Consignee: 1
  • BIS Marking - Yes
  • CM/L No. with validity period - 2531748
  • Type - Gas Cartridge Type
  • Extinguishing Media - Powder Based
  • Clean Agents Based Extinguishing Media - NA
Other Specifications Download Specification
Conformity To Standard IS:15683:2006 With Latest Amdmnt.
BIS Marking Yes
CM/L No. With Validity Period 2531748
Type Gas Cartridge Type
Trolley Without Trolley
Extinguishing Media Powder Based
Foam Based Extinguishing Media NA
Powder Based Extinguishing Media BC
Clean Agents Based Extinguishing Media NA
Expellant Medium CO2 Based
Fire Extinguisher Capacity( Foam Based/Water Based) NA Ltrs
Powder Based Fire Extinguisher Capacity 6 Kg
Carbon Dioxide Based Fire Extinguisher Capacity NA Kg
Clean Agents Fire Extinguisher Capacity NA Kg
Weight Of Filled Portable Fire Extinghuisher 9.2 Kg
Test Pressure For Foam Based/Powder(N≥20) / CO2 Based Fire Extinguisher(N≥35) 35 Bar
Burst Pressure,Min 90 Bar
Discharge Range For Class A Fire Extinguisher(≥2)/Class B (≥1) 2.8 Meters
Effective Discharge Time For Fire Extinguisher, Min 20 Seconds
Fire Rating For Class -A Fire Extinguisher 3A
Fire Rating For Class -B Fire Extinguisher 21B
Fire Extinguisher Suitable For Class -C Fire NO
Fire Extinguisher Suitable For Class -D Fire NO
Fire Extinguisher Suitable For Class -K Fire NO
Rechargebale YES
Color Coding Red
Availability Of Test Report From Central Govt./NABL/ILAC Accredited Lab To Prove Conformity To Specification YES
Test Report No. 2531748
Test Report Date 09/11/2017
Name Of The Lab BUREAU OF INDIAN STANDARDS
Address Of The Lab MANAK BHAWAN NEW DELHI
Operating Temperature -10 C to + 55 C ° C
Fire Extinguisher Suitable For Class -E Fire NO

Price Dekho Price Dekho Price List in india