× All the transactions performed on 2.0 is available here. To access Market click "Home".

online ups 3 kva (apc)(src3kuxi with 65ah x 6)

` 88,101.00

  • Offered Price: ` 97890.00
  • MRP: `109180.00

APC 3 KVA ONLINE UPS,120 MINUTES BACKUP,AUTO SHUTDOWN FACILITY ,INPUT POWER RANGE 140 - 280V, NETWORK MANAGEMENT THROUGH NETWORK CARD,CONFIGURABLE OUTPUT POWER,double conversion true online ups with igbt technology based rectifier and inverter both.

  • Availability: 100 In Stock
  • Min. Qty. Per Consignee: 1
  • Technology - IGBT-PWM without inbuilt isolation transformer
  • Input Power - single phase 160V - 260V sinewave,50Hz
  • Output power - single phase 230V 1 sinewave,50Hz
  • Minimum VAH - 4680 VAH
  • 20% Overload limit for minimum 10 minutes - Yes
Other Specifications Download Specification
Rating In KVA 3 KVA
Technology IGBT-PWM without inbuilt isolation transformer
Input Power single phase 160V - 260V sinewave,50Hz
Output Power single phase 230V 1 sinewave,50Hz
Backup Time 120 Minutes
Minimum VAH 4680 VAH
Voltage Regulation From No Load To Full Load 1 %
Inbuilt Isolation Transformer No (only for IGBT-PWM Technology)
20% Overload Limit For Minimum 10 Minutes Yes
50% Overload Limit For Minimum 1 Minutes Yes
Total Harmonic Distortion(THD) <3 %
Overall Efficiency 92 %
Type Of Battery SMF-VRLA conforming to JISC:8702(Pt.I,II&III)
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted 1.2 mm
Degree Of Protection IP21
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal Yes
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. Yes
Maximum Overshoot And Under Shoot Of Output Rated Voltage 4
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage Yes
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current Yes
Movable Trolly For Batteries Without trolley but with Rack
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs Yes
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) Yes
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. Yes
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. Yes
Type Test Certificate No. CMD-5/CRS 2015-0532/R-83000450
Type Test Certificate Date 14/07/2015
Name Of Lab BIS
Address Of Lab 9 BAHADUR SHAH ZAFAR MARG NEW DELHI 2
Supply & Commissioning FREE OF COST AT CONSIGNEE LOCATION
Warranty 2 Years

Price Dekho Price Dekho Price List in india