BHARTI-SENCO IRON REMOVAL PLANT FOR 12000 LPH FOR TUBEWELLS , PRODUCTION WELLS AND OVERHEAD TANKS APPROVED FORM MINISTRY OF DRINKING WATER AND SANITATION DEPARTMENT GOVERNMENT OF INDIA AND TESTED BY CSIR, GOI..
Other Specifications Download Specification | |
---|---|
Iron Removal Unit | Without |
Prefilter Provided With Flushing Valve In The Iron Removal Unit | NO |
Iron Removal Unit Suitable For Water Supply Equipment | Tubewell |
Discharge Capacity Of The Iron Removal Equipment | 12000 LPH |
Material Of Body Of Iron Removal Equipment | FRP |
Diameter Of Vessel Of Iron Removal Equipment | 1073 +/- 30 mm |
Height Of Vessel Of Iron Removal Equipment | 1800 +/- 30 mm |
Number Of Iron Removal Vessel | ONE Nos |
Minimum Thickness Of Vessel Of Iron Removal Equipment | 0 mm |
Material Of Strainer Plate Of Iron Removal Equipment | 0 |
Diameter Of Strainer Plate Of Iron Removal Equipment | 0 mm |
Minimum Thickness Of The Strainer Plate Of Iron Removal Equipment | 0 mm |
Number Of Strainers For Filtration In Strainer Plate Of Iron Removal Equipment | 0 Nos |
Number Of Strainers For Backwash In Strainer Plate Of Iron Removal Equipment | 0 Nos |
Material Of Strainer In Strainer Plate Of Iron Removal Equipment | 0 |
Quantity Of Iron Removal Media In Iron Removal Vessel | 480 +/- 50 Kg |
Quantity Of Filter Media In Iron Removal Media | 100 +/- 10 Kg |
% Free Space In The Vessel (Top And Bottom) In Iron Removal Vessel | 25 +/- 5 |
Back Wash Valve In Iron Removal Vessel | Automatic Operated Valve System connected to Electric Supply and operated by a timer |
The Accumulated Ferric Is Removed From The Media While Back Washing | YES |
Maximum Iron Content Of Inlet Water | 20 ppm |
Maximum Iron Content Of Outlet Water | 0.3 ppm |
Process By Which Iron Is Removed From Water By Iron Removal Media | 1. Iron removal media works through oxidation process. 2. Ferrous is oxidized to ferric state and gets filtered in the media which acts as a filter bed also. |
Life Of Iron Removal Media | 4 Years |
Cost Of Refilling Of Iron Removal Media | Rs. 795.00 PER KG Rupees |
Life Of Iron Removal Unit | 10 Years |
Protective Coating Of Iron Removal Vessel | UV Protective Coating |
Inlet Pipe Size Of Iron Removal Unit | 65 mm |
Space Required For Installation Of Iron Removal Unit | 2 Square Metres |
Number Of Valves In Iron Removal Unit | ONE Nos |
Materal Of Valve Of Iron Removal Unit | ABS/HDPE |
Diameter Of The Valve In Iron Removal Unit | 65 mm |
Pressure Gauge In Iron Removal Unit | YES |
Pressure Release Valve In Iron Removal Unit | YES |
Maximum Line Water Pressure At Ambient Temperature In Iron Removal Unit | 6 Kg/square cm |
Weight Of Iron Removal Unit | 700 +/- 70 Kg |
Warranty Period Of Iron Removal Unit | 4 Years |
Arsenic Removal Unit | Without |
Discharge Capacity Of The Arsenic Removal Unit | 0 LPH |
Arsenic Removal Unit Suitable For Water Supply Equipment | Tubewell |
Material Of Arsenic Removal Vessel | 0 |
Diameter Of Arsenic Removal Vessel | 0 mm |
Height Of Arsenic Removal Vessel | 0 mm |
Minimum Thickness Of Arsenic Removal Vessel | 0 mm |
Number Of Arsenic Removal Vessel | 0 Nos |
Material Of Strainer Plate Of Arsenic Removal Vessel | 0 |
Diameter Of Strainer Plate Of Arsenic Removal Vessel | 0 mm |
Minimum Thickness Of The Strainer Plate Of Arsenic Removal Vessel | 0 mm |
Number Of Strainers For Filtration In Arsenic Removal Strainer Plate | 0 Nos |
Material Of Strainer In Arsenic Removal Strainer Plate | 0 |
Quantity Of Arsenic Removal Media In Arsenic Removal Vessel | 0 Kg |
Media Used For Removal Of Arsenic From Water | 0 |
% Free Space In The Vessel (Top And Bottom) In Arsenic Removal Vessel | 0 |
Maximum Arsenic Content Of Inlet Water | 0 ppm |
Maximum Arsenic Content Of Outlet Water | NA ppm |
Life Of Arsenic Removal Media | 0 Years |
Cost Of Refilling Of Arsenic Removal Media | 0 Rupees |
Life Of Arsenic Removal Unit | 0 Years |
Protective Coating Of Arsenic Removal Vessel | 0 |
Inlet Pipe Size Of Arsenic Removal Unit | 0 mm |
Space Required For Installation Of Arsenic Removal Unit | 0 Square Metres |
Number Of Valves In Arsenic Removal Unit | 0 Nos |
Materal Of Valve In Arsenic Removal Unit | 0 |
Diameter Of The Valve Of Arsenic Removal Unit | 0 mm |
Pressure Gauge In Arsenic Removal Unit | NO |
Pressure Release Valve In Arsenic Removal Unit | NO |
Maximum Line Water Pressure At Ambient Temperature In Arsenic Removal Unit | 0 Kg/square cm |
Weight Of Arsenic Removal Unit | 0 Kg |
Warranty Period Of Arsenic Removal Unit | 0 Years |
Iron Removal Media Conform To International Standard | National Science Foundation, USA |
Arsenic Removal Media Conform To International Standard | DIN EN 15029 |
Does The Arsenic Media Have Toxicity Leaching Characteristic Procedure Certificate | YES |
Field Testing Kit For Testing Iron & Arsenic Is Provided | YES |