× All the transactions performed on 2.0 is available here. To access Market click "Home".

2kva online ups 120mins with repair of isolation transformer (consul neowatt)(finch 2kva)

` 55,800.00

  • MRP: `65000.00

True Double Online Conversion Microprocessor control optimizes reliability Input Power Factor Correction Output Power Factor 0.8 Wide Input Voltage 110 V- 300 VF Converter Mode Available ECO mode for energy saving only available for 1-3KVA F Generator Compatible Adjustable Battery Number only available and up models Smart SNMP works well with either USB or RS 232 together Comprehensive display allows easy monitoring and access of UPS status Optional isolation transformer available..

  • Availability: 100 In Stock
  • Min. Qty. Per Consignee: 10
  • Technology - IGBT-PWM without inbuilt isolation transformer
  • Input Power - single phase 160V - 260V sinewave,50Hz
  • Output power - single phase 230V 1 sinewave,50Hz
  • Minimum VAH - 4800 VAH
  • 20% Overload limit for minimum 10 minutes - Yes
Other Specifications Download Specification
Rating In KVA 2 KVA
Technology IGBT-PWM without inbuilt isolation transformer
Input Power single phase 160V - 260V sinewave,50Hz
Output Power single phase 230V 1 sinewave,50Hz
Backup Time 120 Minutes
Minimum VAH 4800 VAH
Voltage Regulation From No Load To Full Load 1 %
Inbuilt Isolation Transformer No (only for IGBT-PWM Technology)
20% Overload Limit For Minimum 10 Minutes Yes
50% Overload Limit For Minimum 1 Minutes Yes
Total Harmonic Distortion(THD) 3 %
Overall Efficiency 90 %
Type Of Battery SMF-VRLA conforming to JISC:8702(Pt.I,II&III)
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted 1.2 mm
Degree Of Protection IP21
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal Yes
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. Yes
Maximum Overshoot And Under Shoot Of Output Rated Voltage 4
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage Yes
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current Yes
Movable Trolly For Batteries Without trolley but with Rack
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs Yes
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) Yes
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. Yes
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. Yes
Type Test Certificate No. R-41045829
Type Test Certificate Date 27.07.2016
Name Of Lab BIS
Address Of Lab Manak Bhavan, Newdelhi
Supply & Commissioning 10
Warranty 3 Years

Price Dekho Price Dekho Price List in india