94 Efficiencydouble-ConversionmodeSave Rs 20k Every YearSave Even More In Green Mode,98 Eff3ph Or 1ph Input Site Configurable0.9 Power Factor 9kW OutputSeparate Bypass Input Allows HotStandby OperationAPC Online 10kVASRC10kUXIIntroducing State Of The Art, Next Gen Online UPS1234Standby OperationHigh-Power Charger 3kW MaxSMF/Tubular Battery Selectable40-70Hz Input Frequency RangeGraphical LCD Easy-To-Use Interface192V Battery, Single StringSmartSlot For All Management CardoptionsEPO, USB, RS232C, Dry ContactsRack/Tower Convertible, 3U In RackAir Filter User Maintain-Able. 16 Nos Of 12V -65AH SMF Battery For 120-MIN Battery Backup. Make - Exide. Rack And Interlink Cable.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 10 KVA |
Technology | IGBT-PWM without inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V 1 sinewave,50Hz |
Backup Time | 120 Minutes |
Minimum VAH | 800 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | No (only for IGBT-PWM Technology) |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 3 % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | With |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 1718289 |
Type Test Certificate Date | 30/03/2015 |
Name Of Lab | CSA |
Address Of Lab | USA |
Supply & Commissioning | YES |
Warranty | 2 Years |