Green Lines outstanding features Pure sine wave output ECO mode to save energy Rotatable LCD display design Optional AS400 relay card 19rack mount kit available for all models Tower / Rack multi-configuration forflexible installation Microprocessor control guarantees high reliability Adopting high frequency full bridge topology for high steady performance High input power factor correction Selectable various output range and operating mode Cold start function Inbuilt static bypass enhance better protection for critical load Built-in dry contact / RS-232 / EPO communication port SNMP allows for web-based remote or monitoring management Optional USB communication port Optional Enable to extend run time with scalable external battery pack Overload, short-circuit, and over heat protection Hot-swappable battery design Compact size with high over all efficiency.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 2 KVA |
Technology | MOSFET-PWM with inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V 1 sinewave,50Hz |
Backup Time | 120 Minutes |
Minimum VAH | 2420 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 92 % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | With |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 2965 |
Type Test Certificate Date | 27/01/2009 |
Name Of Lab | ELECTRONICS TEST & DEVELOPMENT CENTRE |
Address Of Lab | G T ROAD NEAR IOC DEPOT AMBALA CANTT 133001 |
Supply & Commissioning | UPS & Batteries shall be installed by our Engineer at site, but site shall be got prepared for Input & output electrical work by the consignee / Indentor |
Warranty | 2 Years |