20 KVA online ups 60 min. back ups time (LUMINOUS)(20 KVA with 60 min back up)

` 299,720.00

  • MRP: `450000.00

20 KVA Online Ups With Back Up Time 60mins Suitable For THREE Phase AC Input And Single Phase AC Output.

  • Availability: 5 In Stock
  • Min. Qty. Per Consignee: 1
  • Rectifier - IGBT Based
  • Operating Voltage - 380/400/415V Volt
  • Maximum Input Voltage Range - +/- 10 Percentage Standard, +/-4 or 6 or 8 or 10 Percentage (Programmable) %
  • Input THD - <5 Percentage at Full Load %
  • Power Factor Of UPS - > 0.98 at Load >50 Percentage
Other Specifications Download Specification
General Requirement: True On-line Double Conversion With A Large Input Voltage Range (low Line Transfer Down To 110 Vac) Isolates Sensitive Equipment From Power Fluctuations While Minimizing Transfers To Increase Battery Life. Independently Controlled Maintenance Bypass Is Designed To Provide Maximum System Availability To Critical Equipment By Allowing Transfer Of Connected Equipment To An Alternate Power Path. The UPS Can Then Be Turned Off And Removed From Service With No Interruption Of Power To Connected Equipment Yes
Rectifier IGBT Based
Operating Voltage 380/400/415V Volt
Maximum Input Voltage Range +/- 10 Percentage Standard, +/-4 or 6 or 8 or 10 Percentage (Programmable) %
Nominal Input Frequency 47-70 Hz Hz
Input THD <5 Percentage at Full Load %
Dual Mains Input Yes
Maximum Load 20 KVA
Power Factor Of UPS > 0.98 at Load >50 Percentage
Cold Start Yes
Input Power Factor Correction Yes
Inverter Output IGBT Based
Output Power Rating 380/400/415V
Output Voltage 380/400/415V Volt
Frequency 50/60Hz +/-0.05 percentage in free running Hz
Efficiency In Battery Operation >94 Percentage %
Efficiency At Full Load (AC-AC) >95 Percentage %
Efficiency At 50 Percentage Full Load (AC-AC)% >95 Percentage
Load Power Factor 0.9 power factor keeps machines performing flawlessly when running on battery power
Overload Capacity 125 Percentage for 1 minute and 150 Percentage for 30 seconds
Output Voltage Tolerance +/-1 Percentage static and +/- 5 Percentage at 100 Percentage load step %
Communication Interface Network management card needs to be provided
Control Panel The UPS Should have an Emergency Power Off Switch built in
Audible On battery, low battery, overload
Mains Fail/On Battery Yes
Battery Low On battery, low battery, overload
Overload Yes
Replace Battery Yes
Visual Yes
On Mains Yes
Mains Fail/On Battery Yes
Battery Fault Yes
Overload/Trip Yes
Back Up 30 minutes on full load
Battery Type SMF-VRLA
Extended Battery Capability Yes
Web /SNMP Management Card Yes
Management Software Yes
Protection Class IP20
Certification IS09001 and ISO14001 and cULus and CE RoHS and Federal Communications Commission - Documentary proof to be submitted alongwith tender copy