2KVA INVERTER CUM UPS WITH 02 NOS.-12V 150AH BATTERIES, VOLTAGE RANGE 140-270V PLUS/MINUS 5V, PURE SINE WAVE CHAGRING CURRENT 15 A PLUS/MINUS 2, PROTECTIONS- ELECTRONICS OVERLOAD, SHORT CIRCUIT PROTECTION, BATTERY DEEP DISCHARGE PROTECTION, BATTERY REVERSE POLARITY PROTECTION , BATTERY OVER/UNDER CHARGE PROTECTION, MCB AT OUTPUT OR HIGHER CONFIGURATION WITH 2 YEARS ONSITE WARRANTY.
Other Specifications Download Specification | |
---|---|
Rating In KVA & Min. VAH Capacity Of Battery | 2 KVA/8640 VAH |
Technology | MOSFET-PWM |
Inverter Governing Specification | Generally conforming to IS:13314 |
Input | Single Phase sine wave(120 to 260 V) |
Output | Single Phase sine wave 230 V |
Inverter Efficiency | 90 % |
Energy Star Rating | 3 |
Total Harmonic Distortion | 3 |
Overload Of Rated Load | 10 |
Overload Time | 10 Minutes |
Battery Cut-off Voltage To Protect From Overdischarge | 10.5 Volt |
Degree Of Protection | IP 21 |
Climatic Test Report As Per Clause 7.10.1 Of IS 13314 | yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab | Yes |
Type Test Certificate No. | 354791 |
Type Test Certificate Date | 27.02.2014 |
Name Of Lab | NTH |
Address Of Lab | GHAZIABAD |
Type Of Battery | Tubular battery confirming to IS:13369 |
Backup Time | 180 Minutes |
Type Of Enclosure | CRCA Steel |
Thickness Of Sheet For Enclosure | 1.2 mm |
Trolley | with trolley |
Trolley Material | CRCA Steel |
Thickness Of Sheet For Trolley | 1.2 mm |