Portable Fire Pump 275LPM. SPECIFICATION of ITEM As per IS 942 1982 Reaffirmed 2005. Light Weight Heavy duty Portable Fire Pump for the purpose of fire fighting / rescue operations. Exhaust priming centrifugal pump with dual carrying handles capable of discharging water at least at rate of 275 LPM, having a pumping capacity of not less than 4 Kgf/cm. abPump shall be capable of lifting the water from 3 mtr in not more than 1 min and shall be fully automatic.acThe pump should have efficient cooling system to permit the pump to run continuously for Two hours. adTwin starter type self starter and manual eqpt starter. Easy to start by one person..
Other Specifications Download Specification | |
---|---|
Functional Conformity To Indian Standrad For Floating Pump | IS: 942: latest |
Centrifugal Pump | Yes |
Continuous Run And Directly Coupled To Engine | Yes |
Water Discharge | 1400 litres/min. |
Delivery Head | 10 Metres |
Casing Material | Powder coated Aluminium alloy |
Discharge Solids Upto | 15 mm |
Standard Equipment Water Resistant Air Cleaner And Muffler With Pump. | Yes |
Engine Specification (Four Stroke Engine) | Petrol |
Ignition | Transistorized |
Cooling | Air cooled |
Horse Power Of Engine(HP)(on The Basis Of Min.discharge,max. Delivery Head,efficiency Of Pump And Coupling | 12 HP |
AUTOMATIC Float Controlled Throttle | Yes |
Compression Release Valve | Yes |
Recoil Starter | Yes |
Fuel Tank Capacity For Continuous Run Of Minimum One Hour. | 2 |
Fuel Gauge | Yes |
Float Assembly Material -High Density Polyethylene Shell Filled With | Polyurethane foam(closed cell) |
MARKed With Photo Luminescent Tape For Visibility In Darkness | Yes |
Pump Shall Not Sink Even Float Is Damaged | Yes |
Dry Weight Of Floating Pump | 5 Kg |
Minimum Water Depth To Operate | 25 mm |
Service Warranty For Parts From Date Installation | 5 Years |
Product Warranty | 2 Years |
Engine Shall Meet Applicable Environmental Protection Norms And Emission Standards. | Yes |
Availability Of Type Test Report To Prove Conformity Of Parameters To The Specification From Any ILAC/NABL Accredited/Central Gov. LAB. | 26 |
Test Certificate No. | ALB/45/205-16 |
Test Report Date | 01/12/2017 |
Name Of The Lab Where Test Conducted. | Fire Test & Research Laboratory |