USED POWDER FOR 90 MAP. TESTED TO 35kgs/cm2. CHARGE PRESSURE 14 kgf/cm2. CARE AND MAINTENANCE AS PER IS2190-2010. TEMPERATURE -20C TO 55C. PROPELLENT GAS NITROGEN..
Other Specifications Download Specification | |
---|---|
Conformity To Standard | IS:15683:2006 With Latest Amdmnt. |
BIS Marking | Yes |
CM/L No. With Validity Period | CM/L 2927672 13.10.2018 |
Type | Stored Pressure |
Trolley | Without Trolley |
Extinguishing Media | Powder Based |
Foam Based Extinguishing Media | NA |
Powder Based Extinguishing Media | ABC |
Clean Agents Based Extinguishing Media | NA |
Expellant Medium | N2 Based |
Fire Extinguisher Capacity( Foam Based/Water Based) | NA Ltrs |
Powder Based Fire Extinguisher Capacity | 4 Kg |
Carbon Dioxide Based Fire Extinguisher Capacity | NA Kg |
Clean Agents Fire Extinguisher Capacity | NA Kg |
Weight Of Filled Portable Fire Extinghuisher | 6.5 Kg |
Test Pressure For Foam Based/Powder(N≥20) / CO2 Based Fire Extinguisher(N≥35) | 35 Bar |
Burst Pressure,Min | 55 Bar |
Discharge Range For Class A Fire Extinguisher(≥2)/Class B (≥1) | 4 Meters |
Effective Discharge Time For Fire Extinguisher, Min | 17 Seconds |
Fire Rating For Class -A Fire Extinguisher | 2A |
Fire Rating For Class -B Fire Extinguisher | 21B |
Fire Extinguisher Suitable For Class -C Fire | YES |
Fire Extinguisher Suitable For Class -D Fire | NO |
Fire Extinguisher Suitable For Class -K Fire | YES |
Rechargebale | YES |
Color Coding | Red |
Availability Of Test Report From Central Govt./NABL/ILAC Accredited Lab To Prove Conformity To Specification | YES |
Test Report No. | 140912CV13004711 |
Test Report Date | 20.10.2014 |
Name Of The Lab | NABL |
Address Of The Lab | MANGOLPURI DELHI |
Operating Temperature | -20° C to + 55° C ° C |
Fire Extinguisher Suitable For Class -E Fire | YES |