Input specificationsOutput specificationsUPS model SRC3KUXINominal input voltage 230 VInput frequency 40 - 70 HzInput connection HardwireInput voltage range 100 load 160 V - 280 VInput voltage range 50 load 100 V - 280 VInput power factor 100 load 0.99 typicalInput power factor 100 load inparallel system 0.95Input protection Thermal circuit breakerUPS model SRC2KUXISR C3KUXIOutput power capacity 1600 W / 2000 VA 2400 W / 3000 VANominal output voltage 230 VOther programmable voltages 220/240 VEfficiency at rated load 91 93Efficiency at rated load in parallelsystem 90 91Output voltage regulation 1 staticOutput voltage distortion 1 linear load, 5 non-linear loadCrest factor 31Waveform SinewaveOutput connection HardwireIEC 320 C13 2 numbersBypass Internal bypas.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 3 KVA |
Technology | IGBT-PWM |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 2400 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 1 % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | R-83000450 |
Type Test Certificate Date | 10-07-15 |
Name Of Lab | BUREAU OF INDIAN STANDARDS |
Address Of Lab | MANAK BHAWAN, NEW DELHI |
Supply & Commissioning | YES |
Warranty | 2 Years |