Assured Reliability True online double-conversion technology to completely isolate theoutput power from all input anomalies DSP based technology to support rapid computation capability and asimplified control circuit for enhanced stability Dual input design to allow different power supply sources forenhanced availability Built-in manual bypass to ensure continuous power to the load even if the UPS fails. UPS is without isolation transformer..
Other Specifications Download Specification | |
---|---|
Rating In KVA | 10 KVA |
Technology | IGBT-PWM |
Input Power | Three phase 300 V - 450V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 10080 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 3% % |
Overall Efficiency | 91 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | IR/10213013(8110493607/DELTA/UPS-20KVA-1R |
Type Test Certificate Date | 06-09-2013 |
Name Of Lab | TUV India Pvt. Ltd, New DElhi |
Address Of Lab | New Delhi |
Supply & Commissioning | 320+ |
Warranty | 4 Years |