INPUT -110 VAC -300va, OUTPUT - 220 ,230 ,240 VAC , BACKUP TIME - 30 Min,60, Min ,90 Min 120 Mins, INBUILT ISOLATION TRANSFORMER NA, 130 percentage OVERLOAD LIMIT FOR MINIMUM 1 MINUTES -Yes, 110 percentage OVERLOAD LIMIT FOR MINIMUM 10 MINUTES yes, TOTAL HARMONIC DISTORTION THD in percentage 3 to 5 percentage, OVERALL EFFICIENCY 92 percentage, TYPE OF BATTERY - SMF VRL, MINIMUM THICKNESS OF M.S.SHEET ENCLOSURE DULY PAINTED -1.6 MM, DEGREE OF PROTECTION - ip20, PROTECTION OF OVER VOLTAGE,SHORT CIRCUIT OVER LOAD AT UPS OUTPUT TERMINAL Yes, PROTECTION FOR UNDER VOLTAGE AT BATTERY TERMINAL AT 10.5V PER 12 V BATTERY yes, MAXIMUM OVERSHOOT AND UNDER SHOOT OF OUTPUT RATED VOLTAGE -110 to 300 percentage, INDICATORS FOR MAINS PRESENCE,BATTERY CHARGING AND DISCHARGING,OUTPUT OVER LOAD, LOW BATTERY VOLTAGE - LCD Display, DIGITAL METERING IN UPS FOR AC INPUT VOLTAGE,OUTPUT AC VOLTAGE,CURRENT,FREQUENCY,BATTERY VOLTAGE AND CURRENT - LCD Display, MOVABLE TROLLY FOR BATTERIES - yes..
Other Specifications Download Specification | |
---|---|
Rating In KVA | 2 KVA |
Technology | MOSFET-PWM |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 2496 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 3 to 5 % |
Overall Efficiency | 92 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | With |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | R 67000361 |
Type Test Certificate Date | 19.01.2016 |
Name Of Lab | Bureau of Indian Standards |
Address Of Lab | Manak Bhavan, 9 Bahadur Shah Jafar Marg, New Delhi - 110002. |
Supply & Commissioning | Yes |
Warranty | 2 Years |