× All the transactions performed on 2.0 is available here. To access Market click "Home".

Carbon-di-Oxide (CO2) type Fire Extinguisher 2 Kg. Capacity (firefite)(BFE/02A/0020)

` 4,675.00

  • MRP: `7200.00

"FIRE FITE" BRAND CARBON DIOXIDE TYPE Fire Extinguisher 2 Kg. capacity as per IS 15683:2006 complete with all the fittings and accessories with ISI Mark, CE Approved Cylinder conforming to IS: 7285 ISI Marked,with CCOE Approval Valve conforming to IS: 3224 ISI Marked and CCOE approval complete with Initial charge. Available with Screw Down Valve; Temperature Range : -30?C to +55?C; Fire Rating: 8B.

  • Availability: 1,000 In Stock
  • Min. Qty. Per Consignee: 10
  • BIS Marking - Yes
  • CM/L No. with validity period - 7336371 31/07/2017
  • Type - Stored Pressure
  • Extinguishing Media - Carbon Dioxide Based
  • Clean Agents Based Extinguishing Media - NA
Other Specifications Download Specification
Conformity To Standard IS:15683:2006 With Latest Amdmnt.
BIS Marking Yes
CM/L No. With Validity Period 7336371 31/07/2017
Type Stored Pressure
Trolley Without Trolley
Extinguishing Media Carbon Dioxide Based
Foam Based Extinguishing Media NA
Powder Based Extinguishing Media NA
Clean Agents Based Extinguishing Media NA
Expellant Medium CO2 Based
Fire Extinguisher Capacity( Foam Based/Water Based) NA Ltrs
Powder Based Fire Extinguisher Capacity NA Kg
Carbon Dioxide Based Fire Extinguisher Capacity 2 Kg
Clean Agents Fire Extinguisher Capacity NA Kg
Weight Of Filled Portable Fire Extinghuisher 8 Kg
Test Pressure For Foam Based/Powder(N≥20) / CO2 Based Fire Extinguisher(N≥35) 250 Bar
Burst Pressure,Min 450 Bar
Discharge Range For Class A Fire Extinguisher(≥2)/Class B (≥1) 2 Meters
Effective Discharge Time For Fire Extinguisher, Min 9 Seconds
Fire Rating For Class -A Fire Extinguisher NA
Fire Rating For Class -B Fire Extinguisher 8B
Fire Extinguisher Suitable For Class -C Fire YES
Fire Extinguisher Suitable For Class -D Fire NO
Fire Extinguisher Suitable For Class -K Fire NO
Rechargebale YES
Color Coding Red
Availability Of Test Report From Central Govt./NABL/ILAC Accredited Lab To Prove Conformity To Specification YES
Test Report No. BFRC/RTG/FE/10
Test Report Date 04/08
Name Of The Lab BFRC
Address Of The Lab Mysore
Operating Temperature -30° C to + 55° C ° C
Fire Extinguisher Suitable For Class -E Fire NO

Price Dekho Price Dekho Price List in india