Microcomputer-Chip basedHigh Frequency Design ensures Low Switching Losses Purity of Sine-Wave Ultra-fast Transient Response Very Low Noise IGBT in Charger section Earthing Protection Double Convertion INPUT 155V 280 V AC Single phase 45 60 Hz. 230VAC 1.0 Single Phase 50 Hz 0.1 Crystal Controlled 3.0 KVA ,0.8 lagging to unity,For 100 step load change output stays within 5 and recovers within cycle,On-board Panel Meter to display following parameters Output Voltage Input load status Battery status bar Load status bar, Battery Status Bar, Fault Diagnostic on LCD Panel Input output Frequency Online Battery Test Pure Sine Wave,Total Harmonic Distortion less than 2 for linear load.Total Harmonic Distortion less than 5 for non-linear load 100 Continuous 150 for 30 seconds 0 to 50C. 95 R.H. MaximumOur UPS has passed Environmental Test From DefenceLa.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 3 KVA |
Technology | IGBT-PWM |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 2016 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | Total Harmonic Distortion less than 2% for linear load. • Total Harmonic Distortion less than 5% for non-linear load % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | MUM-0001777 |
Type Test Certificate Date | 02/01/2017 |
Name Of Lab | NSIC |
Address Of Lab | MUMBAI |
Supply & Commissioning | 40 |
Warranty | 1 Years |