Motwane 5KPI 5KV -Diagnostic Insulation Tester with PI and DAR Measurements.
Other Specifications Download Specification | |
---|---|
Type | Hand Held |
Measurement Range | 200 K Ohm to 1 T Ohm |
Test Voltage | 250, 500, 1000, 2500 and 5000 Volt |
AC/DC Voltage Measurement | 600 Volt |
AC/DC Voltage Measurement Resolution | 0. 1 % |
AC/DC Voltage Measurement Accuracy | 2 % |
Auto Discharge Time | Less than 0.5 Second |
Live Circuit Detection | Live circuit indicator 30 V to 600v ACDC,50 Hz |
Pass Fail Function | Yes |
Data Logging | more than 99 locations |
Software | Available |
Safety Rating | Category III 600 V of IEC 61010 |
Leakage Current | 2 milliamper |
Operating Temperature Range | 0°C to 55°C Degree C |
Operating Humidity (RH) | <95RH, Non condensing % |
Power Requirements | Battery Operated |
Type Of Battery | Internal Rechargeable Battery |
PC Interface | Available |
Standard Accessories Supplied With The Equipment | 3 x 3m test leads for Earth, Guard and Line connection with large insulated clamps 1.5m Main power cord Mains protected fuse Instruction Manual Carrying Bag |
Dimensions (H X W X L) | 195mm x 290mm x 360mm mm x mm x |
Weight | 5000 gms |
Availability Of Test Reports From Central Govt / NABL Approved / ILAC Acredited Lab To Prove Conformity To The Specification Including Environmental Tests As Under : (a) Dry Heat : For 16 Hrs. At A Temp. Of 55 Degree C In Accordance With IS:9000/part-3/section-5/1977 (reaffirmed In 2007). (b) Cold Test : For 4 Hrs. At A Temp. Of -20 Degree C In Accordance With IS:9000/part-2/section-4/1977 (reaffirmed In 2007). (c) Damp Heat (Cyclic)Test : For 2 Cycles Of 24 H Each At A Temp. Of 40 Degree C & 95% RH In Accordance With IS:9000/part-5/section-1/ 1991 (reaffirmed In 2007). After Environmental Conditioning Sequence As Above And A Recovery Period Of Two Hours, The Instrument Shall Be Checked For Complete Functional Parameters, Which Should Be With In Limits.(Test Reports Are To Be Furnished When Demanded By Buyer) | Yes |
Test Report No. | provided at the time of supply |
Test Report Date | provided at the time of supply |
Name Of The Lab | provided at the time of supply |
Warranty | 1 |