DCP type Fire extinguisher cap. 6 Kg. filled with SBC powder confirms to IS 4308 Applicable classes of fire B C, Gross Weight 10.3 Kg, empty Weight 4.3 Kg, Can Height 540mm, Diameter 150 10mm, CO2 gas Cartridge of 120 gm confirms to IS 4947, Controllable discharge mechanism with EPDM Hose Open Nozzle, Discharge Time 20 Sec, Jet Range 4.5 Meters, Average Discharge is 90, Fire rating B Rating 34B, Can Construction Deep drawn MIG Welding technology, CE Marked Brass forged Squeeze grip type valves with Auto safety release at 24 bar About 950 gm. wt. and safety Pin is of SS material, Internal Coating - Epoxy Powder coating, External Coating - Pure Polyester Powder coating UV Resistant, Sheet metal thickness 1.8 mm, Confirms to IS 15683-2006 and ISI Marked..
Other Specifications Download Specification | |
---|---|
Conformity To Standard | IS:15683:2006 With Latest Amdmnt. |
BIS Marking | Yes |
CM/L No. With Validity Period | 3802657, 31.03.2018 |
Type | Gas Cartridge Type |
Trolley | Without Trolley |
Extinguishing Media | Powder Based |
Foam Based Extinguishing Media | NA |
Powder Based Extinguishing Media | BC |
Clean Agents Based Extinguishing Media | NA |
Expellant Medium | CO2 Based |
Fire Extinguisher Capacity( Foam Based/Water Based) | NA Ltrs |
Powder Based Fire Extinguisher Capacity | 6 Kg |
Carbon Dioxide Based Fire Extinguisher Capacity | NA Kg |
Clean Agents Fire Extinguisher Capacity | NA Kg |
Weight Of Filled Portable Fire Extinghuisher | 10.5 Kg |
Test Pressure For Foam Based/Powder(N≥20) / CO2 Based Fire Extinguisher(N≥35) | 35 Bar |
Burst Pressure,Min | 55 Bar |
Discharge Range For Class A Fire Extinguisher(≥2)/Class B (≥1) | 2 Meters |
Effective Discharge Time For Fire Extinguisher, Min | 8 Seconds |
Fire Rating For Class -A Fire Extinguisher | NA |
Fire Rating For Class -B Fire Extinguisher | 34B |
Fire Extinguisher Suitable For Class -C Fire | YES |
Fire Extinguisher Suitable For Class -D Fire | NO |
Fire Extinguisher Suitable For Class -K Fire | NO |
Rechargebale | YES |
Color Coding | Blue |
Availability Of Test Report From Central Govt./NABL/ILAC Accredited Lab To Prove Conformity To Specification | YES |
Test Report No. | 110269 |
Test Report Date | 23.05.2012 |
Name Of The Lab | Fire Test and Research Laboratory |
Address Of The Lab | Sir Chhotu Ram Bhawan, Sector-32, Gurgaon, Haryana-122001 |
Operating Temperature | -30° C to + 55° C ° C |
Fire Extinguisher Suitable For Class -E Fire | YES |