Full range over current protection.Low power consumption. Stable performance and anti-dropping capacity. With original design double display. Application These meters can be widely used in home, school, smelting. Communications, manufacturing, petroleum refining industry. National defense, electricity and chemical industries. Type of Product-Digital AC/DC Clamp Meter, DC Current Range-0-1000 A, DC Voltage Range-400 mV-600 V, AC Current Range-0-1000 A, AC Voltage Range - 400 mV-750 V Capacitance Range-40 n, F-100F Frequency - 10 Hz-10 MHz, Temperature Range - 20 to 1000C Max. DC Current Range - 601-1000 A Max. DC Voltage Range - 0-600 V. Max AC Current Range - 601-1000 A. Max AC Voltage Range - 601-750 V. Model No - MTQ-999. Resistance Range Ohm 0-40 M.
Other Specifications Download Specification | |
---|---|
Type | Hand Held |
Display | Backlit |
Measurement Type | True RMS |
AC Current Measurement Range | 0 to 999.9 Ampere |
AC Current Measurement Accuracy | + or - 2 % |
AC Voltage Measurement Range | 0 to 1000 Volt |
AC Voltage Measurement Accuracy Upto 600 Volts | + or - 1 % |
AC Voltage Measurement Accuracy Beyond 600 Volts | + or - 1.5 % |
Inrush Current (Integration Time) | 100 millisecon |
DC Current Measurement Range | 0 to 999.9 Ampere |
DC Current Measurement Accuracy | + or - 2 % |
DC Voltage Measurement Range | 1000 Volt |
DC Voltage Measurement Accuracy | + or - 1 % |
Resistance Measurement Range | 0 to 4000 Ohm |
Resistance Measurement Accuracy | + or - 1.5 % |
Continuity | < or = 30 Ohm |
Frequency Measurement Range | 10 to 400 |
Frequency Measurement Accuracy | + or - 0.5 |
Jaw Size (Dia In Closed State) | 55 |
Satety Rating | Category III 600 V of IEC 61010 -2-D31 |
Operating Temperature Range | 15-65 Degree C |
Operating Humidity (RH) | 85 % |
Power Requirements | Battery Operated |
Safety Certification (Certificate To Be Furnished When Demanded By Buyer) | UL |
Standard Accessories Supplied With The Equipment | yes |
Dimensions (H X W X L) | 188x123x55 mm x mm x |
Weight | 2.5 gms |
Availability Of Test Reports From Central Govt / NABL Approved / ILAC Acredited Lab To Prove Conformity To The Specification Including Environmental Tests As Under : (a) Dry Heat : For 16 Hrs. At A Temp. Of 55 Degree C In Accordance With IS:9000/part-3/section-5/1977 (reaffirmed In 2007). (b) Cold Test : For 4 Hrs. At A Temp. Of -20 Degree C In Accordance With IS:9000/part-2/section-4/1977 (reaffirmed In 2007). (c) Damp Heat (Cyclic)Test : For 2 Cycles Of 24 H Each At A Temp. Of 40 Degree C & 95% RH In Accordance With IS:9000/part-5/section-1/ 1991 (reaffirmed In 2007). After Environmental Conditioning Sequence As Above And A Recovery Period Of Two Hours, The Instrument Shall Be Checked For Complete Functional Parameters, Which Should Be With In Limits.(Test Reports Are To Be Furnished When Demanded By Buyer) | Yes |
Test Report No. | 21454 |
Test Report Date | 21-02-2017 |
Name Of The Lab | Star Labs |
Warranty | 1 Year |