Trolley mounted water mist cum caf fire fighting system 50 ltr.Model SG 01/50CE marked and approved for live electrical fire as per EN-3 Suitable for Class-A, Class-B and Live Electrical Fire works on 8 bar operating pressure with a lancing distance of min 10 mtrs..
Other Specifications Download Specification | |
---|---|
Conformity To Standards | DIN EN 1866-1:2007-10 |
Cylinder Capacity | 6 Ltrs |
Mounting Type | Trolley mount |
The Trolley Mounted Configuration Shall Have Water Tank, Compressed Air Cylinder And Gun Mounted On A Free Moving Trolley Provided With Strong Wheels As Specified In DIN EN 1866-1:2007-08 Standards. Trolley Mounted Shall Be Supplied With Two Air Cylinders. | Yes |
Pressure Type | Low |
Compound | Standard.AFFF |
Type Of Foam | Standard Foam as per UL 162 or IS 4989 Standards |
If Special Foam Mention The Compostion For Special ,otherwise Put NA | NA |
Commercial Brand Name Of The Special Foam (fire Extinguishing Medium) As Per Accredited Laboratory Test Report Wherein II B Fire Rating Achieved, To Be Declared. | SAFEGUARD |
Spreading Coefficient For Standard AFFF Compound Shall Be +3 Minimum | Yes |
The Concentration Of Compound Shall Be Nominal 6% | Yes |
Fire Rating For Trolley Mounted II B And Di Electric. With Marking Of Fire Class A & B As Per EN 3-7 Standard | Yes |
Extinguishing Medium | Water Mist & CAF |
Extinguishing Gun Material | Stainless steel |
Extinguishing Gun Weight -2000 Gms Approx. | yes grams |
Pressure Vessel Material | Stainless steel |
Pressure Vessel Capacity | 50 Ltrs |
Compressed Air Cylinder Capacity At 300 Bar | 6 Ltrs |
Pressure Gauge To Monitor Air Cylinder Pressure | Yes |
Compressed Air Cylinder Material | Steel |
"Length Of Hose " | 5 Meter |
The Air Hoses Shall Be Suitable For Minus 40 Deg C To 100 Deg C Temperatures | yes |
Lancing Distance Of Gun | 12 Meter |
Flow Rate (must Be In Range Of 0.42 To 0.50) | .43 Ltrs per second |
Minimum Operating Time In Full Throttle | 100 seconds |
Maximum Weight Of Fully Charged System | 90 kg |
Main Components: Pressure Vessel To Hold The Media With Safety Valve, Compressed Air Cylinder Couped With A Reducer, Hose Pipes For Discharge Of Water Mist Media, Extingushing Gun | Yes |
System Shall Be Designed For Maximum Operating Temperature TSmax And Minimum Operating Temperature TSmin Of 60 Deg C Or More And 5 Deg C Or Less Respectively And Certified By The Manufacturer Accordingly | Yes |
"The Air Cylinders Shall Have PESO, Nagpur Approval " | Yes |
Availability Of Test Report To EN Standard | Yes |
Test Certificate No. | SG/001 |
Test Report Date | 01/01/17 |
Name Of Lab Where Test Conducted | ADVANCE |
Dynamics Working Pressure | 3 Bar |