Rated Capacity1 KVA / 900 WattsInput Input Voltage Range Load 50118 295 V 5 VInput Voltage range Load 50160 295 V 5 VFrequency40 70 Hz PhaseSingle Phase with GroundPower Factor 0.99 @ full load Output Voltage Range208 / 220 / 230 / 240 V ACFrequency Range Synchronized RangeFrequency Range Battery Mode47 53 Hz or 57 63 Hz50 Hz 0.1 Hz or 60Hz 0.1 HzTHD Linear Load 2THD Non Linear Load 4Overload 110, 30s turn to Bypass Mode 150 instant turn to BypassCrest Factor31 MaxShort Circuit Protection5 cycles turn Off Inverter, no transfer to Bypass,provide Alarm AC Mode, 5 cycles turn Off Inverter,provide Alarm Battery Mode, Input Fuse blown or Breaker actionWaveformPure SinewaveTransfer time AC Mode to Battery ModeInverter to Bypass ModeZero 4 ms Efficiency85 92.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 1 KVA |
Technology | MOSFET-PWM with inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 800 VAH |
Voltage Regulation From No Load To Full Load | .95 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | NA % |
Overall Efficiency | 92 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | With |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | NA |
Type Test Certificate Date | NA |
Name Of Lab | NA |
Address Of Lab | NA |
Supply & Commissioning | NA |
Warranty | 1 Years |