High Frequency and Double Conversion Online Technology.High End IGBT Based.High End Micro Controller Based.Wide Input Voltage RangeAdvanced PFC TechnologyAdvanced Battery ManagementAutomatic Battery Charging in UPS Off ModeShort Circuit and Overload ProtectionSmart RS232 Communication with monitoring softwareSNMP Card Slot OptionalOver Temperature Protection.EMI / RFI Noise FilterLCD/LED Display simultaneouslySpecially designed to suit Indian Power and Environment ConditionsGenerator Compatible Supplying Sinewave VoltageIsolation Transformer OptionalDifferent Output Voltage settings.Output Frequency fixed at 50Hz or can be synchronized with Input Frequency.Static Bypass Enable or Disable.Outlets Programmable and Non Programmable.Protection from DC Fan failure.In-built Over Voltage Cut-Off Device..
Other Specifications Download Specification | |
---|---|
Rating In KVA | 3 KVA |
Technology | IGBT-PWM with inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 2340 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 2%to4% % |
Overall Efficiency | 92 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | With |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 4465 |
Type Test Certificate Date | 27/02/2014 |
Name Of Lab | MERICAN SYSTEM REGISTRAR |
Address Of Lab | 5281 Clyde Park Ave SW, Wyoming, MI 49509, USA |
Supply & Commissioning | 3500 |
Warranty | 1 Years |