CyberPower OLS10000EXL is a high-performance UPS featuring online double-conversion topology, which provides seamless pure sine wave power for mission-critical devices such as NAS and servers, DVRs/surveillance systems, transportation and infrastructure, and emergency systems. Its typically integrated in the back office, server room, and data center environment. By manually setting the UPS to ECO Mode, the UPS automatically detects the input power quality and discerns whether it should operate in Line Mode or ECO Mode. Under poor power conditions, the UPS will run in Line Mode, which guarantees the highest level of protection and the best possible power quality. When the input power quality is acceptable, the UPS switches to ECO Mode, which increases the total output power efficiency by up to 96. The product is equipped with a Maintenance Bypass Switch. By flipping the switch, the power supply is safely transferred to utility. This allows service personnel to carry out fast on-.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 10 KVA |
Technology | IGBT-PWM with inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 60 Minutes |
Minimum VAH | 10000 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 2 % |
Overall Efficiency | 95 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 38935-G |
Type Test Certificate Date | 27.02.2014 |
Name Of Lab | NTH |
Address Of Lab | GHAZIABAD |
Supply & Commissioning | UPS & Batteries shall be installed by our Engineer at site, but site shall be got prepared for Input & output electrical work by the consignee / Indentor. |
Warranty | 2 Years |