Automation for power analysis and hardware of lights.
Other Specifications Download Specification | |
---|---|
Type Of Power Analyzer | Three phase |
Display Type | LCD Backlit |
Display Mode | LCD DISPLAY |
Number Of Current Channels | 3 Nos. |
Number Of Voltage Channels | 3 Nos. |
Facility To Measure RMS Voltage | Available |
Measurable Voltage Range | 120-285 Volts |
Measurable Voltage Accuracy | 5% |
Measurable Voltage Resolution | 0.1 Volts |
Facility To Measure RMS Current | Available |
Measurable Current Range | 100 Ampere |
Measurable Current Accuracy | 5% |
Measurable Current Resolution | 0.1 Ampere |
Facility To Measure Active, Reactive And Apparent Power | Available |
Maximum Power That Can Be Measured | 20 KW |
Power Accuracy | 5% |
Power Resolution | 0.1 Watt |
Facility To Measure Active, Reactive And Apparent Energy | Available |
Facility To Measure Sag(dips) And Swell(surge) | Available |
Facility To Measure Frequency | Available |
Frequency Range That Can Be Measured | 50 Hz |
Facility To Measure Total Harmonic Distortion | Available |
Accuracy In Measurement Of Total Harmonics Distortion | 5% |
Resolution In Measurement Of Total Harmonics Distortion | 0.1 |
Facility To Measure Inter Harmonics | Available |
Order(n) To Which Facility To Measure Harmonics Available | 30 |
Facility To Measure Power Factor | Available |
Accuracy In Measurement Of Power Factor | 5% |
Facility To Measure Distortion Factor | Available |
Accuracy In Measurement Of Distortion Factor | 5% |
Facility To Measure Ripple Factor | Available |
Accuracy In Measurement Of Ripple Factor | 5% |
Facility To Measure Voltage And Current Unbalance | Available |
Facility To Measure Inrush Current | Available |
Facility To Measure Flicker | Available |
Facility To Measure Crest Factor | Available |
Measurable Crest Factor Range | 50:1 |
Measurable Crest Factor Accuracy | 5% |
Measurable Crest Factor Resolution | 0.1 |
Screen Memory | 2KB |
Data Transfer Software Provided For Analysis On PC | Yes |
Internal Memory | 2048 MB |
Type Of Battery Used | LI-ION |
Battery Backup | 8 Hours |
Power Supply(volts In AC) | 230 |
Weight Of The Analyser | 600 Grams |
Dimensions(LXWXH) | 23X23X15 cmXcmXcm |
Provision For External SD Card | Yes |
Operating Temperature Range | 0-50 degree celsius |
Operating Humidity | 70% % |
All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | Yes |
Details Of All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | 10 |
Compliance To IEC 61000-4-30 | Yes |
Category Of Safety Rating | CAT-3 |
Dry Heat Test As Per IS :9000(Part 3/Section 5) | Yes |
Damp Heat(cyclic Test): Two Cycles Of 24 Hours Each As Per IS: 9000(Part 5/section 1) | Yes |
Cold Test At -20 Degree C For Four Hours As Per IS: 9000(Part2 /section 4) | Yes |
Availability Of Type Test Report From Central Govt. /NABL/ILAC Accredited Lab. To Prove Confirmity To The Specification. | Yes |
Type Test Report No. | AE55468 |
TTC Report Date | 15/11/2017 |
Name Of Lab | SHREE INFRA |
Address Of Lab | SHREE INFRA, SILTARA ROAD, PLOT NO -6, CG |
Interface | LCD TYPE |