Autoronica High Frequency Online UPS Systems are designed and manufactured for IT grade equipments and Data banks. These UPS are equipped with advanced SMART technology features like Microprocessor based controls, True RS-232 port with optional SNMP compatibility for remote monitoring and control of UPS parameters and actions. Our High Frequency Online UPS Systems are available from 1 KVA to 10 KVA..
Other Specifications Download Specification | |
---|---|
Rating In KVA | 1 KVA |
Technology | IGBT-PWM |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 252 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 3% on linear load % |
Overall Efficiency | 91 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | ETDC(MH)/TR/T&M//115 |
Type Test Certificate Date | 01-12-2008 |
Name Of Lab | ETDC |
Address Of Lab | B-108, Indl. Area, Phase-8, SAS Nagar (Mohali) |
Supply & Commissioning | Not required, as UPS has inbuilt battery and UPS is plug & play type |
Warranty | 1 Years |