Power Quality Analyzer with precision Current clamps.
Other Specifications Download Specification | |
---|---|
Type Of Power Analyzer | Three phase |
Display Type | LCD Backlit |
Display Mode | Transient Display |
Number Of Current Channels | 4 Nos Nos. |
Number Of Voltage Channels | 5 Nos Nos. |
Facility To Measure RMS Voltage | Available |
Measurable Voltage Range | 1 to 1000 Volts Volts |
Measurable Voltage Accuracy | 0.1 % |
Measurable Voltage Resolution | 0.01 Volts Volts |
Facility To Measure RMS Current | Available |
Measurable Current Range | 0.5 to 6000 Amperes Ampere |
Measurable Current Accuracy | 0.5 % |
Measurable Current Resolution | 0.1 Ampere Ampere |
Facility To Measure Active, Reactive And Apparent Power | Available |
Maximum Power That Can Be Measured | 6,000,000 KW KW |
Power Accuracy | 1 % |
Power Resolution | 0.1 Watt Watt |
Facility To Measure Active, Reactive And Apparent Energy | Available |
Facility To Measure Sag(dips) And Swell(surge) | Available |
Facility To Measure Frequency | Available |
Frequency Range That Can Be Measured | 50 to 3000 Hz Hz |
Facility To Measure Total Harmonic Distortion | Available |
Accuracy In Measurement Of Total Harmonics Distortion | 0.1 % |
Resolution In Measurement Of Total Harmonics Distortion | 0.1 % |
Facility To Measure Inter Harmonics | Available |
Order(n) To Which Facility To Measure Harmonics Available | DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 |
Facility To Measure Power Factor | Available |
Accuracy In Measurement Of Power Factor | 0.1 % |
Facility To Measure Distortion Factor | Available |
Accuracy In Measurement Of Distortion Factor | 0.1 % |
Facility To Measure Ripple Factor | Available |
Accuracy In Measurement Of Ripple Factor | 0.1 % |
Facility To Measure Voltage And Current Unbalance | Available |
Facility To Measure Inrush Current | Available |
Facility To Measure Flicker | Available |
Facility To Measure Crest Factor | Available |
Measurable Crest Factor Range | 1 to 10 |
Measurable Crest Factor Accuracy | ± 5 % |
Measurable Crest Factor Resolution | 0.01 |
Screen Memory | 100 |
Data Transfer Software Provided For Analysis On PC | Yes |
Internal Memory | 8000 MB MB |
Type Of Battery Used | Li-ion |
Battery Backup | 7 hours Hours |
Power Supply(volts In AC) | 230 |
Weight Of The Analyser | 2000 Grams Grams |
Dimensions(LXWXH) | 26.5 x 19 x 7 cmXcmXcm cmXcmXcm |
Provision For External SD Card | Yes |
Operating Temperature Range | 0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery degree celsius degree celsius |
Operating Humidity | +10 °C ~ +30 °C: 95% RH non-condensing ,+30 °C ~ +40 °C: 75% RH non-condensing ,+40 °C ~ +50 °C: 45% RH non-condensing % % |
All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | Yes |
Details Of All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | Main Unit, 5 Voltage Leads with crocodile clips, 4 Current Clamps, 3 Current Clamps, Mains Adapter, |
Compliance To IEC 61000-4-30 | Yes |
Category Of Safety Rating | CAT III 1000 V, CAT IV 600 V |
Dry Heat Test As Per IS :9000(Part 3/Section 5) | Yes |
Damp Heat(cyclic Test): Two Cycles Of 24 Hours Each As Per IS: 9000(Part 5/section 1) | Yes |
Cold Test At -20 Degree C For Four Hours As Per IS: 9000(Part2 /section 4) | Yes |
Availability Of Type Test Report From Central Govt. /NABL/ILAC Accredited Lab. To Prove Confirmity To The Specification. | Yes |
Type Test Report No. | 2204521 |
TTC Report Date | 10/09/2017 |
Name Of Lab | FLUKE |
Address Of Lab | USA |
Interface | USB |