Eaton 93E Double Conversion True Online VFI class UPS System, 60kVA / 54kW 400V, 50 Hz, Input 3 Phase, Output 3 Phase, IGBT based rectifier and inverter based design offering the following key features -Low THDi, High Input Power Factor, High AC-AC Efficiency, Soft Start capability, Advanced Battery Management technology ABM, Communication and Remote Monitoring capability through LAN, WAN, Easy Load Testing at site without requiring load banks, Modular, Scalable, Redundant Architecture, DC Battery Circuit Breaker, Transformer free Technology.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 60 KVA |
Technology | IGBT-PWM |
Input Power | Three phase 300 V - 450V sinewave,50Hz |
Output Power | 3 phase 400 V ±1% with alternative user setable setting of 380V+-1%,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 48000 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 5% % |
Overall Efficiency | 98 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 19615814001 |
Type Test Certificate Date | 2015 |
Name Of Lab | TUVRheinland |
Address Of Lab | 82/A, WEST WING, 3rd MAIN ROAD, ELECTRONICS CITY, PHASE 1, BANGALORE 560100 |
Supply & Commissioning | Inclusive |
Warranty | 1 Years |