PQA2100 / PQA2100E Power Quality Analyzer is the professional portable device to measure and analyze the power system quality, supply the harmonics analysis and power quality data analysis, also provide big memory for the data storage, which is used to make the long term logger measuring to power system. The PC software can simply upload the data to PC for full analysis.
Other Specifications Download Specification | |
---|---|
Type Of Power Analyzer | Three phase |
Display Type | LCD Backlit |
Display Mode | Digital |
Number Of Current Channels | 3 Nos. |
Number Of Voltage Channels | 3 Nos. |
Facility To Measure RMS Voltage | Available |
Measurable Voltage Range | 1000 Volts |
Measurable Voltage Accuracy | +/- 0.5% |
Measurable Voltage Resolution | 0.1V RMS Volts |
Facility To Measure RMS Current | Available |
Measurable Current Range | 3000 Ampere |
Measurable Current Accuracy | +/- 1% |
Measurable Current Resolution | 1A RMS Ampere Ampere |
Facility To Measure Active, Reactive And Apparent Power | Available |
Maximum Power That Can Be Measured | 200 GWH KW |
Power Accuracy | +/- 1.5 |
Power Resolution | 0.1 Watt Watt |
Facility To Measure Active, Reactive And Apparent Energy | Available |
Facility To Measure Sag(dips) And Swell(surge) | Available |
Facility To Measure Frequency | Available |
Frequency Range That Can Be Measured | 50 Hz |
Facility To Measure Total Harmonic Distortion | Available |
Accuracy In Measurement Of Total Harmonics Distortion | 1 |
Resolution In Measurement Of Total Harmonics Distortion | 1 |
Facility To Measure Inter Harmonics | Available |
Order(n) To Which Facility To Measure Harmonics Available | +/- 0.1 |
Facility To Measure Power Factor | Available |
Accuracy In Measurement Of Power Factor | +/- 0.03 |
Facility To Measure Distortion Factor | Available |
Accuracy In Measurement Of Distortion Factor | +/- 5% |
Facility To Measure Ripple Factor | Available |
Accuracy In Measurement Of Ripple Factor | 1 |
Facility To Measure Voltage And Current Unbalance | Available |
Facility To Measure Inrush Current | Available |
Facility To Measure Flicker | Available |
Facility To Measure Crest Factor | Available |
Measurable Crest Factor Range | 1.0-2.8 |
Measurable Crest Factor Accuracy | +/- 5 |
Measurable Crest Factor Resolution | 0.01 |
Screen Memory | 1 |
Data Transfer Software Provided For Analysis On PC | Yes |
Internal Memory | 8GB MB |
Type Of Battery Used | 4.4AH LI-ION |
Battery Backup | 6 Hours |
Power Supply(volts In AC) | 230 |
Weight Of The Analyser | 1600 Grams |
Dimensions(LXWXH) | 262*173*66 mm cmXcmXcm |
Provision For External SD Card | Yes |
Operating Temperature Range | 40 degree celsius degree celsius |
Operating Humidity | 90 % % |
All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | Yes |
Details Of All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | 3M LONG(5Qty), ALLIGATOR CLIPS(5 Qty), EXTERNAL DC ADAPTER, SOFTWARE CD, USER MANUAL |
Compliance To IEC 61000-4-30 | Yes |
Category Of Safety Rating | CAT III-1000V, CAT IV-600V |
Dry Heat Test As Per IS :9000(Part 3/Section 5) | Yes |
Damp Heat(cyclic Test): Two Cycles Of 24 Hours Each As Per IS: 9000(Part 5/section 1) | Yes |
Cold Test At -20 Degree C For Four Hours As Per IS: 9000(Part2 /section 4) | Yes |
Availability Of Type Test Report From Central Govt. /NABL/ILAC Accredited Lab. To Prove Confirmity To The Specification. | Yes |
Type Test Report No. | 0001 |
TTC Report Date | 09-01-2018 |
Name Of Lab | APLAB |
Address Of Lab | Thane |
Interface | USB LAN |