The Fluke 1621 is an easy-to-use earth ground tester. For ground resistance testing, the 1621 is the first line of defense in detecting reliable ground connections. The unit features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance tests.3-pole Fall-of-Potential earth testing for basic measurements, 2-pole resistance measurements for added versatility, Easily capture values with single-button operation, Ensure accurate measurements with automatic noise voltage detection, Hazardous voltage warning offers increased user protection, Clearly read and record data with a large, backlit display, Rugged holster and design for tough work environments, Portable size allows for easy transportation, Instantly be alerted to measurements outside of your set limit, when you use the adjustable limit setting, 600 V Cat II..
Other Specifications Download Specification | |
---|---|
Display Type | 3 digit LCD display |
Measurable Earth Resistance Range | Auto ranging |
2-pole Method For Resistance Measurement | YES |
3-pole Method For Resistance Measurement | YES |
4-pole Method For Resistance Measurement | NO |
Number Of The Stakes | 3 NOS. |
Material Of The Stakes | Galvenised Steel |
Length Of The Stakes | 46 cm |
Diameter Of The Stakes | 0.8 cm cm |
Number Of The Test Leads | Test Lead-02 with Alligator Clips, Cable Reel-02 Nos. |
Length Of The Test Leads | Test leads- 2.0 M and Reel Cables 25 m - 1 nos and 50 m-01 no. cm |
No. Of Test Leads With Clamps | NO Nos. |
Length Of Test Leads With Clamps | NO cm |
Measuring Range1 For Earth Resistance | 0.15 to 20 Ohms |
Measuring Range2 For Earth Resistance | 200 Ohms |
Measuring Range3 For Earth Resistance | 2 k Ohms |
Measuring Range4 For Earth Resistance | NA Ohms |
Measuring Range5 For Earth Resistance | NA Ohms |
Measuring Range6 For Earth Resistance | NA Ohms |
Measuring Range7 For Earth Resistance | NA Ohms |
Measurable Earth Resistance Resolution For Range1 | 0.01 Ohms |
Measurable Earth Resistance Resolution For Range2 | 0.1 Ohms |
Measurable Earth Resistance Resolution For Range3 | 1 Ohms |
Measurable Earth Resistance Resolution For Range4 | NA Ohms |
Measurable Earth Resistance Resolution For Range5 | NA Ohms |
Measurable Earth Resistance Resolution For Range6 | NA Ohms |
Measurable Earth Resistance Resolution For Range7 | NA Ohms |
Measurable Earth Resistance Accuracy For Range1 | 6 of measured value + 5D ±% reading ± digits |
Measurable Earth Resistance Accuracy For Range2 | 6 of measured value + 5D ±% reading ± digits |
Measurable Earth Resistance Accuracy For Range3 | 6 of measured value + 5D ±% reading ± digits |
Measurable Earth Resistance Accuracy For Range4 | NA ±% reading ± digits |
Measurable Earth Resistance Accuracy For Range5 | NA ±% reading ± digits |
Measurable Earth Resistance Accuracy For Range6 | NA ±% reading ± digits |
Measurable Earth Resistance Accuracy For Range7 | NA ±% reading ± digits |
Stakeless Test(Clamp On) | no |
Facility To Measure Earth Voltage | Not Available |
If Yes,Measurable Earth Voltage Range | NA Volts |
If Yes,Measurable Earth Voltage Accuracy | NA % |
Minimum Open Circuit Output Voltage | 23-24 Volt Volts |
Low Battery Indication | Available |
Over Range Indication | Available |
If Yes,Measurable Earth Voltage Resolution | NA Volts |
Internal Memory | NA |
Type Of Battery Used In The Power Supply | 9 Volt |
Battery Backup Time | Standard Hours |
Battery Charger Provided With The Meter. | NA |
Weight Of The Tester | 850 g grams |
Dimensions(LXWXH) | 11.3X5.4X21.6 cmXcmXcm |
Provision For External SD Card | No |
Interface | NO |
Operating Temperature Range | -10 to 50 degree degree celsius |
Operating Humidity Range | 5-95 % |
All Connecting Cables And Accessories To Be Supplied Along With The Tester. | Yes |
Details Of All Connecting Cables And Accessories To Be Supplied Along With The Tester. | User manual, Two measuring leads with alligator clips, 2 m (6 ft), 01 cable reel of 25m, 01 Cable reel of 50m, Earth Stakes-03 Nos., One battery, 9 V alkaline (LR61), One protective holster, yellow, One CD-ROM, Hard Carrying Case |
Availability Of Type Test Report From Central Govt. /NABL/ILAC Accredited Lab. To Prove Confirmity To The Specification Including Environmental Test Sequence. 1. Dry Heat Test As Per IS :9000(Part 3/Section 5) 2.Damp Heat(cyclic Test): Two Cycles Of 24 Hours Each As Per IS: 9000(Part 5/section 1) 3.Cold Test At -20 Degree C For Four Hours As Per IS: 9000(Part2 /section 4). After Completion Of Environmental Conditioning Sequence As Specified And Recovery Of 2 Hours, The Functional Parameters Of Earth Resistance Meter Shall Be Checked. | Yes |
Type Test Report No. | NABL 011 |
TTC Report Date | 10.01.2018 |
Name Of Lab | ACCUMEN NABL CALIBRATION LAB |
Address Of Lab | New Delhi |