The majority of power problem arises mostly due to sudden dips and under voltage. The online design and wash input range of Uniline IGBT OnLine 5KVA UPS avoid data loss caused by voltage problems. It has a sleek and compact design. The UPS is built in with high quality full time isolation. The isolation transformer and double conversion isolates the output entirely. There is no need for an extra isolation transformer as required in imported systems. It requires an operating temperature from 0 50 degree C and a storage temperature ranging from 0 degree C to 60 degree C. It is an online double conversion UPS type. It offers the protection of automatic shutdown in all major operating system. THE PRICES GIVEN ARE WITHOUT BATTERIES..
Other Specifications Download Specification | |
---|---|
Rating In KVA | 5 KVA |
Technology | IGBT-PWM with inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V 1 sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 4000 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 1 % |
Overall Efficiency | 92 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 38935D |
Type Test Certificate Date | 27.02.2014 |
Name Of Lab | NTH |
Address Of Lab | GHAZIABAD |
Supply & Commissioning | AS PER COMPANY |
Warranty | 1 Years |