motwane 5kv insulation resistance tester- it 51 (motwane)(it 51)

` 57,500.00

  • MRP: `78000.00

Motwane IT 51- 5 KV Insulation Tester along with standard Accessories with PI and DAR Measurement.

  • Availability: 9 In Stock
  • Min. Qty. Per Consignee: 1
  • Measurement Range - 200 K Ohm to 1 T Ohm
  • Test Voltage - 250, 500, 1000, 2500 and 5000 Volt
  • AC/DC Voltage Measurement - 600 Volt
  • AC/DC Voltage Measurement Accuracy - 2 %
  • Pass Fail Function - No
Other Specifications Download Specification
Type Hand Held
Measurement Range 200 K Ohm to 1 T Ohm
Test Voltage 250, 500, 1000, 2500 and 5000 Volt
AC/DC Voltage Measurement 600 Volt
AC/DC Voltage Measurement Resolution 0. 1 %
AC/DC Voltage Measurement Accuracy 2 %
Auto Discharge Time Less than 0.5 Second
Live Circuit Detection NA
Pass Fail Function No
Data Logging NA
Software Not Available
Safety Rating Category III 600 V of IEC 61010
Leakage Current 1 milliamper
Operating Temperature Range -10'C to 55'C Degree C
Operating Humidity (RH) < 95 RH, non condensing max at 40 C %
Power Requirements Battery Operated
Type Of Battery Rechargeable battery Lithium Ion
PC Interface Available
Standard Accessories Supplied With The Equipment Test Leads - 3m ( Red,black,green), calibration certificate and User Manual
Dimensions (H X W X L) 195 * 290 * 360 mm x mm x
Weight 5 gms
Availability Of Test Reports From Central Govt / NABL Approved / ILAC Acredited Lab To Prove Conformity To The Specification Including Environmental Tests As Under : (a) Dry Heat : For 16 Hrs. At A Temp. Of 55 Degree C In Accordance With IS:9000/part-3/section-5/1977 (reaffirmed In 2007). (b) Cold Test : For 4 Hrs. At A Temp. Of -20 Degree C In Accordance With IS:9000/part-2/section-4/1977 (reaffirmed In 2007). (c) Damp Heat (Cyclic)Test : For 2 Cycles Of 24 H Each At A Temp. Of 40 Degree C & 95% RH In Accordance With IS:9000/part-5/section-1/ 1991 (reaffirmed In 2007). After Environmental Conditioning Sequence As Above And A Recovery Period Of Two Hours, The Instrument Shall Be Checked For Complete Functional Parameters, Which Should Be With In Limits.(Test Reports Are To Be Furnished When Demanded By Buyer) Yes
Test Report No. 002
Test Report Date 01/07/2017
Name Of The Lab Factory Calibration Lab
Warranty 1

Price Dekho Price Dekho Price List in india