Microtek UPS JM SW 5 KVA is designed to handle Higher Loads. It runs Load upto 400 Watts. It is best recommended UPS for an Area where Power Cut is frequent. Being Sinewave Output, it has many In-built Protection features such as Overload, Battery Deep Discharge and Short- Circuit.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 5 KVA |
Technology | IGBT-PWM with inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V 1 sinewave,50Hz |
Backup Time | 90 Minutes |
Minimum VAH | 1600 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | No (only for IGBT-PWM Technology) |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 1 % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | ETDC(MH)T&M/293 |
Type Test Certificate Date | 02/01/2013 |
Name Of Lab | ETDC |
Address Of Lab | ETDC,Mohali |
Supply & Commissioning | yes |
Warranty | 2 Years |