I/P -Single Phase 110V-300 V Sinewave 50/60 HZ,O/P - Single Phase 230V 1 Sinewave 50Hz, VOLT REGULATION FROM NO LOAD TO FULL LOAD In Prct -230V /- 1 Static Regulation,INBUILT ISOLATION TRSFMR No,130 Prct OVERLOAD LIMIT FOR MIN 1 Mnts -Yes,110 Prct OVERLOAD LIMIT FOR MIN 10 Mnts - Yes,TOTAL HARMONIC DISTORTION In Prct - 3 On Linear Load, OVERALL EFFY 92 Prct,TYPE OF BATT - SMF-VRLA Conforming To JISC87029Pt.I,II III, MIN THICKNESS OF M.S.SHEET ENCLOSURE -0.9 MM, DEG OF PROTECTION - Ip20, PROTECTION OF OVER VOLT,SHORT CIRCUIT OVER LOAD AT UPS O/P TERMINAL - Yes,PROTECTION FOR UNDER VOLT AT BATT TERMINAL AT 10.5V PER 12 V BATT - Yes, MAX OVERSHOOT AND UNDER SHOOT OF O/P RATED VOLT - NA,INDICATORS FOR MAINS PRESENCE,BATT CHARGING DISCHARGING,O/P OVER LOAD, LOW BATT VOLT - Yes, DIGITAL METERING IN UPS FOR AC I/P VOLT,O/P AC VOLT, CURR FREQY,.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 6 KVA |
Technology | IGBT-PWM without inbuilt isolation transformer |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V 1 sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 0 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | No (only for IGBT-PWM Technology) |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | <3 on Linear Load % |
Overall Efficiency | 92 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | NTS/PPTL/UPS-309/04 |
Type Test Certificate Date | 09-10-2015 |
Name Of Lab | Nisaki Technology Services |
Address Of Lab | No. 46, Park Road, 2nd Main, 10th Cross, Wilson Garden, Bangalore - 27 |
Supply & Commissioning | yes |
Warranty | 2 Years |