× All the transactions performed on 2.0 is available here. To access Market click "Home".

online ups 5 kva Maxipower Uniline UPS without batteries (online ups 5 kva uniline)(online ups 5 kva uniline without batteries)

` 48,850.00

  • MRP: `68490.00

Complete Blackout and Brownout ProtectionAccording to Study by Bells Labs, under voltage sudden dipsrepresent the majority of power problem. Wide Input range Onlinedesign of Uniline UPS prevent data loss caused by outrages brownouts.Salient Features Wide Input Windo Generator Compatible Computer Grade Power Superior Float Cum Boost Charger IGBT Based Hi - Frequency PWM Inverter O/P Distortion 3 Inverter Efficiency 92. High crest factor 4 1 Crystal controlled output frequency 50 Hz 0.01. Low noise 50 db upto 10 KVA Compact, sleek design Backup up to 8 Hrs RS 232 C / SNMP Interface Tested. by Reputed Agencies without batteries.

  • Availability: 2 In Stock
  • Min. Qty. Per Consignee: 1
  • Technology - MOSFET-PWM with inbuilt isolation transformer
  • Input Power - single phase 160V - 260V sinewave,50Hz
  • Output power - single phase 230V 1 sinewave,50Hz
  • Minimum VAH - 4.5 VAH
  • 20% Overload limit for minimum 10 minutes - Yes
Other Specifications Download Specification
Rating In KVA 5 KVA
Technology MOSFET-PWM with inbuilt isolation transformer
Input Power single phase 160V - 260V sinewave,50Hz
Output Power single phase 230V 1 sinewave,50Hz
Backup Time 30 Minutes
Minimum VAH 4.5 VAH
Voltage Regulation From No Load To Full Load 1 %
Inbuilt Isolation Transformer No (only for IGBT-PWM Technology)
20% Overload Limit For Minimum 10 Minutes Yes
50% Overload Limit For Minimum 1 Minutes Yes
Total Harmonic Distortion(THD) 1 %
Overall Efficiency 90 %
Type Of Battery SMF-VRLA conforming to JISC:8702(Pt.I,II&III)
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted 1.2 mm
Degree Of Protection IP21
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal Yes
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. Yes
Maximum Overshoot And Under Shoot Of Output Rated Voltage 4
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage Yes
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current Yes
Movable Trolly For Batteries Without
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs Yes
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) Yes
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. Yes
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. Yes
Type Test Certificate No. 38935D
Type Test Certificate Date 27.02.2014
Name Of Lab NTH
Address Of Lab GHAZIABAD
Supply & Commissioning AS PER COMPANY
Warranty 1 Years

Price Dekho Price Dekho Price List in india