Aska High Pressure Water Mist CAF Fire Extinguisher Backpack Type with Vessel and Air cylinder of Ultralite Carbon Composite with PET Liner 9 Liter Capacity with Special AFFF Compound Fire Rating A63, B233 and E1000V.
Other Specifications Download Specification | |
---|---|
"Conformity To EN 3-7:2004+A1:2007-08 Standards (The Complete System Shall Be Tested For Compliance From An Internationally/nationally Accredited Laboratory For Compliance To All 30 Clauses (3.2, 3.15, 4.2, 4.3, 4.4, 4.5, 6.1, 6.2, 6.3, 7.1.1, 7.1.2, 7.2, 7.3, 7.4, 8.1, 8.2, 9.2, 10.1, 10.2, 10.3, 10.4, 10.5, 10.6.1 & 10.6.2, 14.1, 14.2, 15.2, 15.3, 16.1, 16.2) Of EN 3 - 7:2004 + Al: 2007-08 (E) Standard Mandatorily Applicable For The Complete System.)" | Yes |
Mounting Type | Backpack |
Configuration ( Shall Be Mounted On A Sturdy Frame Suitably Cushioned For Comfort, Provided With Shoulder Pads For Carrying As A Backpack And A Handle To Be Carried By Hand. All Materials Used Shall Be Of Fire Retardant Type. Backpack Shall Be Supplied With Two Air Cylinders.) | Yes |
Model Number As Per Accredited Laboratory Test Report To Be Declared | ASKA HiPress 9 Carbon-E |
Air Cylinder Capacity | 2 Ltrs |
Air Cylinder Pressure | 300 Bar |
Air Cylinder Material | Ultralight Carbon composite with PET Liner |
High Pressure Type (Dynamic Operating Pressure To Be Tested In The Accredited Laboratory Test Report Which Will Be Considered As High Pressure For As Per Clause No. 3.15 Of EN 3 - 7:2004 + Al: 2007-08 (E) Standard.) ≥ 30 For Aluminium Vessel , ≥ 35 For Ultralight Carbon Composite With PET Liner Vessel | 37.6 Bar |
Type Of Foam | Special AFFF Compound conforming to manufacturer own specifications for higher fire rating A55, B233, Spreading coefficient for special AFFF Compound shall be +5 minimum, concentration shall be 6%. |
If Special Foam Mention The Compostion For Special ,otherwise Put NA | Water 96%. 1,2-Ethandiol |
Commercial Brand Name Of The Special Foam (fire Extinguishing Medium) As Per Accredited Laboratory Test Report Wherein Higher Fire Ratings I.e A55,B233, E1000 V (Die Electric Suitability) Achieved, To Be Declared. | ASKA 63 A |
Characteristics Of Extinguishing Medium Of Special AFFF Compound (manufacturer Own Specifications) With Infrared Spectrogram To Be Furnished. | Density 1.04 (kg/dm3), Viscosity 1.35(mm2/s), pH factor 7.8, Refractive index 1.34 at 20 ± 2deg C |
Pressure Vessel Material & Capacity (Nominal Charge) | Ultralite Carbon Composite with PET Liner of 9 liter capacity |
Minimum Wall Thickness Of Aluminimum Alloy Pressure Vessel | 5 mm |
PED Approval As Per Directive 97/23/EC | Yes |
Pressure Vessel Shall Include A Pressure Gauge Fitted On The Vessel (CE Marked From Notified Body). | Yes |
"No Objection Certificate (NOC) For Pressure Vessel From Petroleum And Explosives Safety Organization (PESO) Nagpur " | Yes |
Pressure Vessel Should Have CE Marking From Notified Body | Yes |
Extinguishing Gun Material | Stainless Steel |
If Others Mentions The Material For Extinguishing Gun,otherwise Put NA | NA |
Extinguishing Gun Weight | 750 gram grams |
Lancing Distance Of Gun : More Than 12 Meter | 15 meter |
Length Of EN Marked Hose 1.3 Meter For Backpack System | 1.3 meter |
The Air Hoses Shall Be Suitable For Minus 40 Deg C To 100 Deg C Temperature And EN Mark On Hose | Yes |
Weight Of Fully Charged Backpack System Between 25kg To 27kg Having Corrosion Free Aluminum Alloy Vessel And Below 20 Kg Having Ultralite Carbon Composite With PET Liner Vessel For | 20 kg |
Main Components: Pressure Vessel To Hold The Media With Safety Valve, Compressed Air Cylinder Coupled With A Reducer, Hose Pipes For Discharge Of Water Mist Media, Extinguishing Gun. | Yes |
"System Shall Be Designed For Maximum Operating Temperature TSmax And Minimum Operating Temperature TSmin Of 60 Deg C Or More And 5 Deg C Or Less Respectively And Certified By The Manufacturer Accordingly As Per Clause 7.4 Of EN 3-7:2004+A1:2007-08 Standards As Per The Accredited Test Report For Backpack System. " | Yes |
The Air Cylinders Shall Have PESO, Nagpur Approval | Yes |
Specific Consent Of The OEM For The Value Additions Made Along With A Confirmation That Fire Ratings Of The Equipment Would Not Be Affected By These Value Additions. | Yes |
Test Report No. | 20161319/AS 06 |
Test Report Date | 28-10-2016 |
Name Of ILAC/NABL/Central Govt.Accredited Laboratory Where Test Conducted | MPA DRESDEN |
NOC Letter No. Date Of PESO Nagpur For Pressure Vessel | G.3-42-Misc./2017/428 |
Minimum Operating Time In Full Throttle For Aluminium Alloy Vessel ( Must Be Greater Than Equal To 20 Seconds ) Put NA If Not Applicable | NA seconds |
Minimum Operating Time In Full Throttle For Ultralight Carbon Composite With PET Liner Vessel ( Must Be Greater Than Equal To 28 Seconds ) Put NA If Not Applicable | 29 seconds |