The Fluke 1550C Insulation Resistance Tester Offers Digital Insulation Testing Up To 5 KV, Making Them Ideal For Testing A Wide Range Of High Voltage Equipment Including Switchgear, Motors, Generators And Cables.Fluke Insulation Testers Can Now Conduct The Entire Range Of Test Voltages Specified In IEEE 43-2000 With A Best In Class, 3 Year Warranty And CAT IV 600 V Safety Rating. With Measurement Storage And PC Interface, The 1550C Is The Perfect Tool For Preventative Or Predictive Maintenance Programs Designed To Identify Potential Equipment Failures Before They Occur..
Other Specifications Download Specification | |
---|---|
Type | Hand Held |
Measurement Range | 0.01 M Ohm to 10 G Ohm 0.01 M Ohm to 10 G Ohm 0.01 M Ohm to 10 G Ohm |
Test Voltage | 250, 500, 1000, 2500 and 5000 Volt |
AC/DC Voltage Measurement | 600 Volt |
AC/DC Voltage Measurement Resolution | 0. 1 % |
AC/DC Voltage Measurement Accuracy | 2 % |
Auto Discharge Time | Less than 0.5 Second |
Live Circuit Detection | NA |
Pass Fail Function | Yes |
Data Logging | more than 99 locations |
Software | Available |
Safety Rating | Category III 600 V of IEC 61010 |
Leakage Current | 1 milliamper |
Operating Temperature Range | -20 C To 50 C (-4 F To 122 F) Degree C |
Operating Humidity (RH) | 80 To 31 C Decreasing Linearly To 50 At 50 C % |
Power Requirements | Battery Operated |
Type Of Battery | 12 V Lead-Acid Rechargeable Battery, Yuasa NP2.8-12 |
PC Interface | Available |
Standard Accessories Supplied With The Equipment | Test Cables With Alligator Clips (Red, Black, Green),Infrared Adapter With Interface Cable,FlukeView Forms Basic CD-ROM,AC Power Cord,Soft Carrying Case,English Manual,Users Manual On CD-ROM,Quick Reference Card,Software License Agreement,Registration Card,FlukeView Forms Installation Guide,USB-IR Cable Installation Guide |
Dimensions (H X W X L) | 269 Mm X 277 Mm X 160 Mm (10.6 In X 10.9 In X 6.3 In) mm x mm x |
Weight | 3.7 Kg (8.2 Lb) gms |
Availability Of Test Reports From Central Govt / NABL Approved / ILAC Acredited Lab To Prove Conformity To The Specification Including Environmental Tests As Under : (a) Dry Heat : For 16 Hrs. At A Temp. Of 55 Degree C In Accordance With IS:9000/part-3/section-5/1977 (reaffirmed In 2007). (b) Cold Test : For 4 Hrs. At A Temp. Of -20 Degree C In Accordance With IS:9000/part-2/section-4/1977 (reaffirmed In 2007). (c) Damp Heat (Cyclic)Test : For 2 Cycles Of 24 H Each At A Temp. Of 40 Degree C & 95% RH In Accordance With IS:9000/part-5/section-1/ 1991 (reaffirmed In 2007). After Environmental Conditioning Sequence As Above And A Recovery Period Of Two Hours, The Instrument Shall Be Checked For Complete Functional Parameters, Which Should Be With In Limits.(Test Reports Are To Be Furnished When Demanded By Buyer) | Yes |
Test Report No. | 3945649 |
Test Report Date | 10 Oct 17 |
Name Of The Lab | Fluke |
Warranty | 1 |