Online Double Conversion UPS Topology Energy Saving Technology Generator Compatible Overload Protection Zero Transfer Time Smart Battery Management SBM External Battery Module EBM Surge and Spike Protection EMI and RFI Filtration Phone/ Fax/ Modem/ DSL/ Network Protection LCD Status Display Emergency Power Off EPO Port PowerPanel Management Software SNMP/ HTTP Remote Management Capability Tower Form Factor.
Other Specifications Download Specification | |
---|---|
Rating In KVA | 5.2 KVA |
Technology | MOSFET-PWM |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 120 Minutes |
Minimum VAH | 4000 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 3 % |
Overall Efficiency | 93 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | R-41016861 |
Type Test Certificate Date | 06.07.2015 |
Name Of Lab | BIS |
Address Of Lab | Manak Bhawan, 9, Bahadur Shah Jafar Marg, New Delhi-110002 |
Supply & Commissioning | YES |
Warranty | 2 Years |