The ACPL On-Line UPS system provides Pure Sine Wave and protects its user equipments from impurity of input power supply.AN ISO 9001 2000 14001 2004 CERTIFIED COMPANYACPL On-Line UPS range 1KVA to 200KVAACPL On-Line UPS system is compact with a very good workmanship and users friendly. it is very easy in installation, operation, simple in maintenance, most reliable and compatiable with several Indian power supply and local make DG set.Sailent featuresTrue On-Line Double Conversion UPS system.High frequency PWM designed using IGBT.Wide input Voltage range.Generator compatiable.Float cum Boost Charger.Compact and excellent workmanship.Compatible for all types and capacity of batteries.Smooth and Silent Operation.Soft start facility.Short circuit/over load protection.Immediate response of Pre-sales and Post sales services...
Other Specifications Download Specification | |
---|---|
Rating In KVA | 10 KVA |
Technology | IGBT-PWM |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 7560 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 2 % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | With |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | ETDC/PAT/TEST/0951/2008-09 |
Type Test Certificate Date | 29/01/09 |
Name Of Lab | ETDC |
Address Of Lab | PATNA |
Supply & Commissioning | YES |
Warranty | 2 Years |