× All the transactions performed on 2.0 is available here. To access Market click "Home".

emerson liebert super 400d 60 mins. (emerson vertiv)(super 400d 60 mins)

` 368,000.00

  • MRP: `411650.00

The Liebert Super 400D Is A True On-Line Sine Wave UPS System That Provides The User With Clean Computer Grade Power For Continuous Operation Of His Critical Load, Regardless Of Any Disturbance On The Upstream AC Power With AC To AC Efficiency Of 84 Percent and IP20 protection. The System Offers Many Innovative Features To Give The User Maximum Reliability And Flexibility At The Lowest Operating Cost. With Liebert Super 400D UPS System, You Have Complete Peace Of Mind...

  • Availability: 2 In Stock
  • Min. Qty. Per Consignee: 1
  • Technology - IGBT-PWM
  • Input Power - Three phase 300 V - 450V sinewave,50Hz
  • Output power - single phase 230V ±1% sinewave,50Hz
  • Minimum VAH - 13104 VAH
  • 20% Overload limit for minimum 10 minutes - Yes
Other Specifications Download Specification
Rating In KVA 10 KVA
Technology IGBT-PWM
Input Power Three phase 300 V - 450V sinewave,50Hz
Output Power single phase 230V ±1% sinewave,50Hz
Backup Time 60 Minutes
Minimum VAH 13104 VAH
Voltage Regulation From No Load To Full Load 1 %
Inbuilt Isolation Transformer Yes
20% Overload Limit For Minimum 10 Minutes Yes
50% Overload Limit For Minimum 1 Minutes Yes
Total Harmonic Distortion(THD) %
Overall Efficiency 90 %
Type Of Battery SMF-VRLA conforming to JISC:8702(Pt.I,II&III)
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted 1.2 mm
Degree Of Protection IP21
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal Yes
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. Yes
Maximum Overshoot And Under Shoot Of Output Rated Voltage 4
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage Yes
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current Yes
Movable Trolly For Batteries With
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs Yes
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) Yes
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. Yes
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. Yes
Type Test Certificate No. SMR/TMC/07-08/EN03
Type Test Certificate Date 25-6-07
Name Of Lab SAMEER
Address Of Lab MUMBAI
Supply & Commissioning Yes with installation
Warranty 1 Years

Price Dekho Price Dekho Price List in india