ashok leyland 160kva three phase liquid cooled dg set with amf panel (from - ashok leyland)(csh-a-160-tp-a-cpcb-2)

` 1,330,899.00

  • MRP: `1499680.00

160 KVA Three Phase Silent type DG Set with AMF Control Panel comprising of ASHOK LEYLAND make Engine 4 stroke in-line Liquid cooled engine with rated power output of 197.05 BHP 147 KW with 12 Volt Electric Start. Electronic Governor A-0 Class, 250 liters fuel tank capacity coupled with 160 KVA, 415 Volt, Three Phase, 1500 RPM, 50 Hz Leroy-Somer Alternator with standard accessories....

  • Availability: 100 In Stock
  • Min. Qty. Per Consignee: 1
  • Nominal Rated Capacity - 160 KVA
  • No of Phase( single phase-3.5,5 & 7.5KVA)(single phase or three phase-10,15 b& 20 KVA)(Three Phase-25 to 750 KVA). - Three Phase Phase
  • Make of Engine - Ashok Leyland
  • Type of Engine cooling - Liquid Cooled
  • Capacity of Engine - 5760 cc
Other Specifications Download Specification
Diesel Generating Set Complete With Diesel Engine, Alternator And AMF/MANUAL Control Panel Fitted In Accoustic Enclosure . Pressure Charged Diesel Engine And Alternator Shall Be Closely Coupled Or Provided With Flexible Coupling And Mounted On A Base Plate Of Robust In Construction. yes
Nominal Rated Capacity 160 KVA
No Of Phase( Single Phase-3.5,5 & 7.5KVA)(single Phase Or Three Phase-10,15 B& 20 KVA)(Three Phase-25 To 750 KVA). Three Phase Phase
Make Of Engine Ashok Leyland
Model Number Of Engine AL6DTIDG4
Type Of Engine Cooling Liquid Cooled
Number Of Cylinders 6 nos
No. Of Strokes 4 nos
Capacity Of Engine 5760 cc
Engine Power 5760 cc
Type Of Governer Electronic
Class Of Governer A0
Rated RPM Of Engine 1500 RPM
Overload Capacity For One Hour For Every 11 Hours Continuous Running At Full Load 10 %
Specific Fuel Consumption 214 gm/kwh/h
ISI Marking To IS :10001 For Engine No
BIS License No If Applicable yes
BIS License Date If Applicable No
Starting Voltage 12 volt
Battery Type & Specification low maintenance free to IS 14257 for high cranking performance
Battery Capacity 105 Ah
No Of Batteries 1 Nos
AC GENERATOR(ALTERNATOR) Make Leroy Somer
AC GENERATOR(ALTERNATOR) Model Number LSAP 44.3 H
Rating Of AC Generator 160 KVA
Power Factor Of AC Generator 0.8
Efficiency At Rated Power Factor At 75% Of Full Load 93.1
Compliance Of Alternator To IS:13364(part-1) yes
Type Of Alternator Brush less
Voltage Regulation Grade VG-3
Alternator IP Rating (Batter Than IP-21) IP23
Class Of Insulation H
CONTROL PANEL AMF
Automatic Mains Failure (AMF) Control Panel, Where Applicable, Shall Be Able To Start Up The DG Set And Transfer The Load On To The DG Set On Mains Failure Without Requiring Any Human Intervention. Similarly On Restoration Of Mains Supply,it Shall Be Able To Transfer The Load To Mains Supply And Switch Off The DG Set Automatically. yes
Control Panel Should Have Protection Against Under Voltage,over Voltage, Under Frequency, Over Frequency, Low Battery Voltage, Over Current, Earthfault, Short Circuit, Phase Sequence Change Etc. yes
Equipped With Suitable Voltmeter,Ammeter,Frequency Meter,power Factor Meter, Battery Caharger Where Battery Is Used, Indicators, Various Switches And Cutout /MCB/MCCB/Contactor/Circuit Breaker Of All Appropriate Rating And Accuracy Class As Per Trade Practice For Better Utility. yes
Pretreated And Powder Coated Accoustic Enclosure Of CRCA Sheet yes
Accoustic Enclosure Of CRCA Sheet Thickness 1.6 mm
Thickness Of Foam 50 mm
Density Of Foam For Sound Insulation 96
Noise Level At 1 Meter 75 db
IP Rating Of Accoustic Control Panel( Batter Than IP-53) INSIDE CANOPY
Anti-Vibration Mountings For Complete DG Set In Case Of Flexible Coupling And For Pressure Charged Engine In Case Of Direct Coupling Shall Be Supplied. yes
Standard Set Of Tools Consisting Of A Set Of 3 Spanners, One Screw Driver,one Standard Plier And One Nose Plier Of Appropriate Size Shall Be Provided To The Consignees Along With DG Sets, yes
Availability Of Type Test Report From Central Government/NABL/ILAC Accridiated Laoratory To Prove Conformity To The Specification For Each Rating For Engine. yes
Test Report Number QF-EPGG/QAD/FR/044
Date Of Issue Of Test Report By Laboratory 16.12.2012
Name And Address Of Laboratory DQA, DGS&D, Banglore
Availability Of Type Test Report From Central Government/NABL/ILAC Accridiated Laoratory To Prove Conformity To The Specification For Each Rating For Alternator. yes
Test Report Number QF-EPGG/QAD/FR/044
Date Of Issue Of Test Report By Laboratory 16.12.2012
Name And Address Of Laboratory DQA, DGS&D, Banglore
DG Sets Shall Meet The Requirements Of Environmental(Protection) Rules 1986 As Laid Down By Min. Of Environment & Forests Read With GSR 371 (E) Dated 17.5.2002,GSR 520(E)dated 1.7.2003 , No.448 (E)dated 12.07.2004 , GSR 771(E) Dated 11.12.2013 GSR 232(E)dated 31.03.2014,Gazette Notification No.167 Dated. 31.03.2014 And Gazette Notification No. 578 Dated. 11.11.2014.in Respect Of Noise And Emission Norms. The Latest Amendments To Above GSRs Shall Be Applicable As And When Amended By Ministry Of Environment And Forest. yes
Warranty 1 Year
Installation ,Commissioning & Testing YES ( For ratings 62.5 KVA and above)
Cable Size For Installation ,3.5C,300 sqmm for Three Phase ,160 KVA sqmm
Foundation Shall Be Of PCC Type With The Ratio Of 4:2:1. The Length And Breadth Of The Foundation Shall Be 300 Mm More From The Respective Length And Breadth Of The DG Set. The Height Of The Foundation Shall Be 400 Mm I.e. 200 Mm Below And 200 Mm Above The Ground Level. T He Foundation Work Shall Be Done By The Firm. yes
ISI Marked PVC Outer Sheathed(FR) Of Type ST-2 Cable (FR Grade C1Catagory)armoured With Aluminium Conductor Having Insulation Of PVC Compound Type -C, Suitable For Rated Voltage At 1100 Volts Grade And Conforming To IS: 1554 (Part-1)/1988(Reaffirmed 2005) Cable And It’s Necessary Laying And Termination Shall Be Done By Firm. For 3-phase DG Sets, 3.5 Core Or Higher Core Cables Shall Be Used. The Current Rating Of The Cables Shall Be As Per Table Attached. Total Length Of The Cable Shall Be Within 30 Meters For DG Sets With Manual Control Panel And Within 60 Metres For DG Sets With AMF Control Panel. yes
Building Suitable Earthing Station And Necessary Connections Shall Be Done By Firm. In Case Of 3 Phase DG Sets, The Total Number Of Earthing Pits/stations Shall Be 4 I.e. 2 For Neutral And 2 For Body-earthing. In Case Of Single Phase DG Sets, The Total Number Of Earthing Station Shall Be 2 And It Shall Be Used For Body-earthing. The Consignee Should Choose Installation Site In Such A Way That The Earthing Stations Can Be Made Within 20 Metres Of The DG Set. Earthing Station Shall Be Typically Built As Per Prevalent Standard Practices. yes
Installation Of Fuel Tank, Battery Charging, And Battery Connection yes
Supply And Installation Of A Change-over Of Suitable Rating For DG Set With Manual Control Panel. yes
Unloading And Placement Of DG Set On Foundation. The Consignee Shall Ensure That The Site Is Located Along A Motorable Road. yes
First Fill Of Lube Oil And All Filters Shall Be Provided By The Firm. The Firm Shall Also Provide 20 Litres Of Diesel For DG Sets Of Rating Upto 15 KVA, 40 Litres For Rating Upto 40 KVA & 50 Litres Of Diesel For DG Sets Of Rating Upto 125 KVA, 100 Litres For Rating Upto 250 KVA And 200 Litres For Ratings More Than 250 KVA. yes
The Consumables Provided By The Firm Cover The Trial Run Of DG Set As Well. The Firm Shall Conduct Trial Run Of The DG Set With The Available Electrical Load At Site. The Trial Run Shall Be For ONE Hour. The Available Electrical Load Shall Be Less Than Or Equal To The Rated Capacity Of The DG Set. yes
Exhaust Piping, Extra Civil Work, Distribution Board Shall Be Provided By Consignee/user. yes
Necessary Approvals, If Any, Shall Be Obtained By The Consignees. yes