online ups with 120 min back up (luminous)(ld1000 120 min back up)

` 62,424.00

  • MRP: `69360.00

I/P -Single Phase 110V-300 V sinewave 50/60 HZ,O/P - Single Phase 230V 1 sinewave 50Hz, BKUP TIME-120 Mins-12 V, 100 ah x 3, VOLT REGULATION FROM NO LOAD TO FULL LOAD in prct -230V /- 1 static regulation,INBUILT ISOLATION TRSFMR No,130 prct OVERLOAD LIMIT FOR MIN 1 Mnts -Yes,110 prct OVERLOAD LIMIT FOR MIN 10 Mnts yes,TOTAL HARMONIC DISTORTION in prct 3 on Linear Load, OVERALL EFFY 86 prct,TYPE OF BATT - SMF-VRLA conforming to JISC87029Pt.I,II III, MIN THICKNESS OF M.S.SHEET ENCLOSURE -0.9 MM, DEG OF PROTECTION - ip20, PROTECTION OF OVER VOLT,SHORT CIRCUIT OVER LOAD AT UPS O/P TERMINAL -Yes,PROTECTION FOR UNDER VOLT AT BATT TERMINAL AT 10.5V PER 12 V BATT - yes, MAX OVERSHOOT AND UNDER SHOOT OF O/P RATED VOLT NA,INDICATORS FOR MAINS PRESENCE,BATT CHARGING DISCHARGING,O/P OVER LOAD, LOW BATT VOLT - Yes, DIGITAL METERING IN UPS FOR AC I/P VOLT,O/P AC VOLT, CURR FREQY,BATT VOLT CURR - Yes.

  • Availability: 22 In Stock
  • Min. Qty. Per Consignee: 20
  • Technology - MOSFET-PWM
  • Input Power - single phase 160V - 260V sinewave,50Hz
  • Output power - single phase 230V ±1% sinewave,50Hz
  • Minimum VAH - 3600 VAH
  • 20% Overload limit for minimum 10 minutes - Yes
Other Specifications Download Specification
Rating In KVA 1 KVA
Technology MOSFET-PWM
Input Power single phase 160V - 260V sinewave,50Hz
Output Power single phase 230V ±1% sinewave,50Hz
Backup Time 120 Minutes
Minimum VAH 3600 VAH
Voltage Regulation From No Load To Full Load 1 %
Inbuilt Isolation Transformer Yes
20% Overload Limit For Minimum 10 Minutes Yes
50% Overload Limit For Minimum 1 Minutes Yes
Total Harmonic Distortion(THD) <3 on Linear Load %
Overall Efficiency 92 %
Type Of Battery SMF-VRLA conforming to JISC:8702(Pt.I,II&III)
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted 1.2 mm
Degree Of Protection IP21
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal Yes
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. Yes
Maximum Overshoot And Under Shoot Of Output Rated Voltage 4
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage Yes
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current Yes
Movable Trolly For Batteries Without
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs Yes
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) Yes
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. Yes
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. Yes
Type Test Certificate No. CRS 201S-26421R-41028819
Type Test Certificate Date 11.01. 2016
Name Of Lab Bureau of Indian Standards
Address Of Lab Manak Bhavan, 9 Bahadur Shah Jafar Marg, New Delhi -110002.
Supply & Commissioning Yes
Warranty 2 Years

Price Dekho Price Dekho Price List in india