Automatic internal bypass Supplies utility power to the connected loads in the event of a UPS power overload or fault.Automatic self-test Periodic battery self-test ensures early detection of a battery that needs to be replaced.Cold-start capable Provides temporary battery power when the utility power is out.Excellent foot print Small UPS footprint provides maximum usage of valuable electrical room floor space Frequency and voltage regulation Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.Generator compatibility Allows you to recharge your battery while on generator power.Green mode Patent-pending operating mode that bypasses unused electrical components in good power conditions to achieve very high operating efficiency without sacrificing any protection...
Other Specifications Download Specification | |
---|---|
Rating In KVA | 1 KVA |
Technology | MOSFET-PWM |
Input Power | single phase 160V - 260V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 432 VAH |
Voltage Regulation From No Load To Full Load | 0.5 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | 10 % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | With |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | CAN BE PROVIDED |
Type Test Certificate Date | CAN BE PROVIDED |
Name Of Lab | CAN BE PROVIDED |
Address Of Lab | CAN BE PROVIDED |
Supply & Commissioning | yes |
Warranty | 2 Years |