Microcomputer-Chip based High Frequency Design ensures Low Switching Losses Purity of Sine-Wave Ultra-fast Transient Response Very Low Noise IGBT in Charger section Earthing Protection Double Convertion 160 V 270 V AC Single phase 45 60 Hz 230VAC 1.0 Single Phase 50 Hz 0.1 Crystal Controlled, 0.8 lagging to unity For 100 step load change output stays within 5 and recovers within 1/2 cycle On-board Panel Meter to display parameters Input /Output Voltage, Input load status, Battery status bar, Load status bar, Fault Diagnostic on LCD Panel, Input / output Frequency, Online Battery Test,Pure Sine Wave, Total Harmonic Distortion less than 2 for linear load.Total Harmonic Distortion less than 5 for non-linear load,100 Continuous 150 for 30 seconds, 0 to 50C. 95 R.H. Maximum,Our UPS has passed Environmental Test From Defence ,CE Marking, ISO9001-2015..
Other Specifications Download Specification | |
---|---|
Rating In KVA | 10 KVA |
Technology | IGBT-PWM |
Input Power | Three phase 300 V - 450V sinewave,50Hz |
Output Power | single phase 230V ±1% sinewave,50Hz |
Backup Time | 30 Minutes |
Minimum VAH | 9360 VAH |
Voltage Regulation From No Load To Full Load | 1 % |
Inbuilt Isolation Transformer | Yes |
20% Overload Limit For Minimum 10 Minutes | Yes |
50% Overload Limit For Minimum 1 Minutes | Yes |
Total Harmonic Distortion(THD) | less than 2% for linear,less than 5% for non-linear load. % |
Overall Efficiency | 90 % |
Type Of Battery | SMF-VRLA conforming to JISC:8702(Pt.I,II&III) |
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted | 1.2 mm |
Degree Of Protection | IP21 |
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal | Yes |
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. | Yes |
Maximum Overshoot And Under Shoot Of Output Rated Voltage | 4 |
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage | Yes |
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current | Yes |
Movable Trolly For Batteries | Without |
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs | Yes |
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) | Yes |
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. | Yes |
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. | Yes |
Type Test Certificate No. | 10 |
Type Test Certificate Date | NSIC |
Name Of Lab | NSIC |
Address Of Lab | MUMBAI |
Supply & Commissioning | 20 |
Warranty | 1 Years |