ETC systems are more efficient and therefore occupies lesser space. ETC systems are more economical in cos. tETC systems are ideal for hard water applications. Storage Tank is made of Stainless steel SS 304L superior grade.Minimum heat loss during night due to 3 target coated Evacuated tubes leads to maximum heat absorbtivity of greater than 98 and the vacuum technology employed ensures minimum heat loss during night time.Easy to install and maintain.Can give an expected life of 15 years provided water quality is good..
Other Specifications Download Specification | |
---|---|
Confirmity To Standards For Solar Water Heating System -Code For Acceptance | IS : 12976:1990 with latest amndmt. |
BIS Approved | No |
If Yes , Mention CM/L No. Otherwise Put NA | NA |
Model Number Of Solar Water Heater System | 1000 LPD |
Solar Water Heating System Compaitabilty With Heat Exchange | Solar Water Heating System with Heat Exchanger |
Region | Type 1 Cold (Areas where ambient temp. reaches 5 degree C or below) |
Rated Capacity In Litres Per Day | 1000 LPD |
Aperture Area Of Collector , Sq. Meteres | 1.8 Sq Meter |
Electrical Heater ( Back Up ) Capacity | 2 kw |
Capacity Of Make Up Tank( SWHS With Heat Exchanger Only ) | 5 Ltrs |
Solar Flat Plate Shall Be BIS Marked And As Per IS :12933/2003 With Amndmt 1 To 3 | Yes |
Type Of Cover Plate Conforming To IS 12933/2003 | Made up of Toughened Glass with thickness 4.00 mm minimum |
Solar Transmittance For Cover Plate At Normal Incidence | 82 % |
Material For Collector Box | Aluminium |
Numbers Of Collectors | 15 |
Minimum Channel Section Thickness For Sides ( For Al Based) MUST BE >=1.4 Mm Otherwise Put 0 For CRCA Material | 2 mm |
Minimum Thickness Of Sheet For Bottom ( For Al Based), MUST BE >=0.45 Mm Otherwise Put 0 For CRCA Material | .50 mm |
Minimum Thickness Of Sheet Used As Support For Glass Retaining ( For Al Based), MUST BE >=1.2 Mm Otherwise Put 0 For CRCA Material | 2 mm |
Thickness Of Sheet For Entire Body ( For Al Based), MUST BE >=1.0 Mm Otherwise Put 0 For CRCA Material | 1 mm |
CRCA Material Thickness, Minimum MUST BE >=0.91 Mm Otherwise Put 0 For Al Material | 0 mm |
Riser And Header Assembly Desigmed For Working Pressure 24.5 K Pa Shall Be Tested For Leakage At A Minimum Hydraulic Pressure Of 490 K Pa | Yes |
Number Of Absorber Sheets Per Collector | 2 |
Numbers Of Header Tubes | 10 |
Numbers Of Riser Tubes | 10 |
Diameter Of Header Tube | 25 mm |
Diameter Of Riser Tube | 12 mm |
Thickness Of Header Tube | .8 mm |
Thickness Of Riser Tube | .7 mm |
Material Of Riser /Header For Absorber | Copper Only |
Distanace Between Risers From Center To Center | 130 mm |
Material Of Sheet For Absorber | Copper |
Collector Box Insulation | Back and sides |
Thermal Resistance Of Insulation In Square Degree For Back Face(must Be Greater Than >=0.96) | 1 W/K m |
Thermal Resistance Of Insulation In Square Degree For Side Face(must Be Greater Than >=0.47) | .5 W/K m |
Gasket And Grommets Shall Confirm To IS 12933/2003 With Latest Amndmt. | Yes |
Material For Hot Water Storage Tank | SS304 |
Name The Material If Choose Others | CRC |
Non Pressure Type Hot Water Storage Tank | Yes |
Position Of Hot Water Tank | Horizontal |
Thickness Of Sheet Of Hot Water Tank | 2mm mm |
Hot Water Tank Insulation Density ( High Density PUF Insulation For 32 Kg/ Meter Cube Or Higher Density | 45 mm |
Hot Water Welding | TIG |
Coating Material For Hot Water Tank | Polyster Epoxy Plus Balck Epoxy based Paint |
Thickness Of Coating | 50 micron |
Tank Stand Material | Mild Steel |
Size Of Tank Stand (L X W X H ) Must Be Greater Than 38 X38 X 4 | 50x50x5 mm3 |
Type Of Heat Exchanger | cage Type |
Material For Heat Exchanger | Copper |
Thickness Of Tube Of Heat Exchanger , Minimum 22 SWG | 22 |
Heat Transfer Rate For Heat Exchanger , Must Be Greater Than 0.24 Sq Meter Per 100 LPD Capacity | .25 |
Numbetrs Of Electrical Heaters ( Back Up Type ) Provided | 2 |
Collector Stand Material | Mild Steel |
Size Of Collector Tank Stand (L X W X H ) Must Be Greater Than 38 X38 X 4 | 40x40x4 mm3 |
System Interconnecting Pipes Material | G I Pipes as per IS 1239 |
If Other Mention The Material For Interconnecting Pipes | 0 |
Size Of Interconnecting Pipes | 2mm mm |
Tank Test Pressure | 2 bar bar |
System Working Pressure | 2 bar Bar |
Inlet And Outlet Valve | Yes |
Temp Gauge( For Hot Water ) | Yes |
Gun Metal Strainer ( For Cold Water ) | Yes |
Water Meter | Yes |
Gasket For Flanges | 3 mm thick gasket of Neoprene |
Electrical Back Up Control Panel | Yes |
Make Of Control Panel | Others |
If Others , Mention The Make Of Control Panel | 0 |
Weight Of Solar Water Heater System | 180 kg |
Availability Of Schematic Drawing | Yes |
Instruction Manual For Installation , Repair And Maintanance | Yes |
Warranty | 1 Years |
Availability Of Test Report As Per IS : 6893-6 (1985) Used For Purcahse Specification For Machine Tools , Part 6 Bench /Pillar Type Drill Machine With Latest Amndmt.from Central Govt./NABL/ILAC Acredited Lab To Prove Confirmity To Specification | Yes |
Test Report No. | 394/2016-17 |
Test Report Date | 20/04/2017 |
Name Of The Lab | NISE |
Address Of The Lab | Gurgaon Haryana |