× All the transactions performed on 2.0 is available here. To access Market click "Home".

emerson liebert 20kva (emerson liebert)(super 400d 10-20kva)

` 269,603.73

  • Offered Price: ` 272327.00
  • MRP: `302586.00

TRUE ON-Line DPS Based UPS With Unity Power Factor.

  • Availability: 50 In Stock
  • Min. Qty. Per Consignee: 5
  • Technology - IGBT-PWM without inbuilt isolation transformer
  • Input Power - Three phase 300 V - 450V sinewave,50Hz
  • Output power - single phase 230V ±1% sinewave,50Hz
  • Minimum VAH - 6480 VAH
  • 20% Overload limit for minimum 10 minutes - Yes
Other Specifications Download Specification
Rating In KVA 20 KVA
Technology IGBT-PWM without inbuilt isolation transformer
Input Power Three phase 300 V - 450V sinewave,50Hz
Output Power single phase 230V ±1% sinewave,50Hz
Backup Time 30 Minutes
Minimum VAH 6480 VAH
Voltage Regulation From No Load To Full Load 1 %
Inbuilt Isolation Transformer No (only for IGBT-PWM Technology)
20% Overload Limit For Minimum 10 Minutes Yes
50% Overload Limit For Minimum 1 Minutes Yes
Total Harmonic Distortion(THD) 5 %
Overall Efficiency 90 %
Type Of Battery SMF-VRLA conforming to JISC:8702(Pt.I,II&III)
Minimum Thickness Of M.S.Sheet Enclosure Duly Painted 1.2 mm
Degree Of Protection IP21
Protection Of Over Voltage,Short Circuit & Over Load At UPS Output Terminal Yes
Protection For Under Voltage At Battery Terminal At 10.5V Per 12 V Battery. Yes
Maximum Overshoot And Under Shoot Of Output Rated Voltage 4
Indicators For Mains Presence,Battery Charging And Discharging,Output Over Load, Low Battery Voltage Yes
Digital Metering In UPS For AC Input Voltage,Output AC Voltage,Current,Frequency,Battery Voltage And Current Yes
Movable Trolly For Batteries Without trolley but with Rack
Dry Heat Test : In Accordance With IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) At 55 Degree C For 16 Hrs Yes
Damp Heat : In Accordance With IS:9000(part 5/sec.2)1981 At Temperature Of 40 Degree C,two Cycles Of (12+12) Hours Each 2007) Yes
Cold Test : In Accordance With IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) At -10 Degree C For 4 Hrs. Yes
Availability Of The Type Test Report From Central Govt. /NABL/ILAC Accredited Lab Covering All Technical Requirements. Yes
Type Test Certificate No. ISO 9001
Type Test Certificate Date 24-10-2002
Name Of Lab Electronics regional test laboratory
Address Of Lab hyderabad
Supply & Commissioning yes
Warranty 1 Years

Price Dekho Price Dekho Price List in india