Fluke 435 II Power Quality and Energy Analyzer as your insurance policy. No matter what goes wrong in your facility, with the 435 II you will always be prepared. Equipped with advanced power quality functions and energy monetization capabilities, there is no electrical issue this model cant handle..
Other Specifications Download Specification | |
---|---|
Type Of Power Analyzer | Single phase |
Display Type | LCD Backlit |
Display Mode | Transient display |
Number Of Current Channels | 5 Nos. Nos. |
Number Of Voltage Channels | 4 Nos. Nos. |
Facility To Measure RMS Voltage | Available |
Measurable Voltage Range | 1 -1000 Volts Volts |
Measurable Voltage Accuracy | 0.5% |
Measurable Voltage Resolution | 0.1 Volts Volts |
Facility To Measure RMS Current | Available |
Measurable Current Range | 0.5 - 6000 Ampere Ampere |
Measurable Current Accuracy | 0.5% |
Measurable Current Resolution | 0.1 Ampere Ampere |
Facility To Measure Active, Reactive And Apparent Power | Available |
Maximum Power That Can Be Measured | 6000 KW KW |
Power Accuracy | 1% |
Power Resolution | 0.1 Watt Watt |
Facility To Measure Active, Reactive And Apparent Energy | Available |
Facility To Measure Sag(dips) And Swell(surge) | Available |
Facility To Measure Frequency | Available |
Frequency Range That Can Be Measured | 60 Hz to 3000 Hz Hz |
Facility To Measure Total Harmonic Distortion | Available |
Accuracy In Measurement Of Total Harmonics Distortion | 0.1% |
Resolution In Measurement Of Total Harmonics Distortion | 0.1% |
Facility To Measure Inter Harmonics | Available |
Order(n) To Which Facility To Measure Harmonics Available | DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 |
Facility To Measure Power Factor | Available |
Accuracy In Measurement Of Power Factor | 0.1% |
Facility To Measure Distortion Factor | Available |
Accuracy In Measurement Of Distortion Factor | 0.1% |
Facility To Measure Ripple Factor | Available |
Accuracy In Measurement Of Ripple Factor | 0.1% |
Facility To Measure Voltage And Current Unbalance | Available |
Facility To Measure Inrush Current | Available |
Facility To Measure Flicker | Available |
Facility To Measure Crest Factor | Available |
Measurable Crest Factor Range | 1 to 10 |
Measurable Crest Factor Accuracy | ± 5 % |
Measurable Crest Factor Resolution | 0.01 |
Screen Memory | 100 |
Data Transfer Software Provided For Analysis On PC | Yes |
Internal Memory | 8 GB MB MB |
Type Of Battery Used | Li-ion |
Battery Backup | 8 Hours Hours |
Power Supply(volts In AC) | 230 |
Weight Of The Analyser | 2000 Grams Grams |
Dimensions(LXWXH) | 26.5 x 19 x 7 cmXcmXcm cmXcmXcm |
Provision For External SD Card | Yes |
Operating Temperature Range | 0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery degree celsius |
Operating Humidity | +10 °C ~ +30 °C: 95% RH non-condensing ,+30 °C ~ +40 °C: 75% RH non-condensing ,+40 °C ~ +50 °C: 45% RH non-condensing % |
All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | Yes |
Details Of All Connecting Cables And Accessories To Be Supplied Along With The Analyzer | 5 voltage probes with Alligator clips & 4 current clamps |
Compliance To IEC 61000-4-30 | Yes |
Category Of Safety Rating | 600V CAT IV 1000V CAT III |
Dry Heat Test As Per IS :9000(Part 3/Section 5) | Yes |
Damp Heat(cyclic Test): Two Cycles Of 24 Hours Each As Per IS: 9000(Part 5/section 1) | Yes |
Cold Test At -20 Degree C For Four Hours As Per IS: 9000(Part2 /section 4) | Yes |
Availability Of Type Test Report From Central Govt. /NABL/ILAC Accredited Lab. To Prove Confirmity To The Specification. | Yes |
Type Test Report No. | 3945658 |
TTC Report Date | 10 Oct 17 |
Name Of Lab | Fluke |
Address Of Lab | USA |
Interface | mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery |